2002-01-14 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
 3) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 4)NOTE: PLEASE CLARIFY EXISITNG LIGHTING
 EMERGENCY LTS/EXITS LTS ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  