| 2002-04-11 00:00:00 | DENIED |
| | REFERENCE: SPC-94 |
| | |
| | 1) RISER DIAGRAM NOT TO CODE. 2ND FLOOR |
| | BATHROOM SHALL NOT WASH PAST WASH MACH- |
| | INE AND LAUNDRY SINK. SEPARATE STACK OR |
| | TIE INTO STACK BELOW W/M & LAUNDRY SINK. |
| | |
| | 2) HEATER PAN REQUIRED FOR HEATER IN |
| | ATTIC. 1" DRAIN LINE SHALL BE REQUIRED |
| | TO BE PIPED OUTSIDE AND TERMINATE 6" |
| | ABOVE GRADE. SEC 507.8.2 |
| | |
| | 3) EVERY ATTIC SPACE IN WHICH MECHANICAL |
| | EQUIPMENT IS INSTALLED SHALL HAVE AN |
| | OPENING AS LARGE AS THE LARGEST PIECE OF |
| | EQUIPMENT. 22"X36" MIN. EVERY PASSAGEWAY |
| | SHALL BE UNOBSTRUCTED AND SHALL HAVE |
| | SOLID CONTINUOUS FLOORING NOT LESS THAN |
| | 24" WIDE FROM OPENING TO EQUIPMENT. ON |
| | THE CONTROL SIDE AND OTHER SIDES WHERE |
| | ACCESS IS NECESSARY FOR SERVICING THE |
| | EQUIPMENT, A LEVEL WORKING PLATFORM EX- |
| | TENDING A MINIMUM OF 30 FROM THE EDGE OF |
| | THE EQUIPMENT WITH A 36" HIGH CLEAR |
| | WORKING SPACE SHALL BE PROVIDED. SECTION |
| | 304.5.2 SMC-97 |
| | |
| | 4) MODEL COUNTYWIDE AMENDMENTS SEC 304.4 |
| | ATTIC INSTALLATION, ALL AIR CONDITIONING |
| | AND HEATING EQUIPMENT INSTALLED IN AN |
| | ATTIC SHALL HAVE AN ACCESSIBLE DISCONNE- |
| | CT SWITCH AND A 110-120 VOLT A/C GROUND- |
| | ING TYPE CONVENIENCE OUTLET CONVENIENT |
| | TO THE GENERAL EQUIPMENT AREA. IN AN |
| | ATTIC, A LIGHT LOCATED ON THE SERVICE |
| | SIDE OF THE EQUIPMENT WICH IS CONTROLLED |
| | BY A SWITCH LOCATED AT THE REQUIRED PASS |
| | AGEWAY OPENING SHALL BE PROVIDED. |
| | |
| | 5) APPLIANCES INSTALLED IN ATTIC SPACES |
| | SHALL BE SUPPORTED FROM THE TOP CHORDS |
| | OF TRUSSED OR ROOF FRAMING OR AS DE- |
| | SIGNED BY A PROFESSIONAL ENGINEER. |
| | |