| Plan Review Notes For Permit 02010316 |
| Permit Number |
02010316 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-15 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | | | --PROVISO-- | | | IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY, PLANS STAMPED BY THEM AND A COPY | | | OF THE RECEIPT SUBMITTED TO CITY OF WEST | | | PALM BEACH BUILDING DEPARTMENT, BEFORE | | | A BUILDING PERMIT CAN BE ISSUED. | | | | | | --PROVISO-- | | | SBC 1506.1SEPARATE ROOFING PERMIT | | | (#02010321).SUBMIT A PRODUCT APPROVAL | | | FOR THE FIBERGLASS SHINGLE ROOF COVERING | | | | | | --PROVISO-- | | | SBC* 1707.4PRODUCT APPROVAL.THE | | | SUBMITTED NOTICE OF ACCEPTANCE | | | NO. 01-0516.10 FOR THE ALUMINUM SINGLE | | | HUNG WINDOW IS MISSING DRAWING SHEET | | | 1 OF 8.SUBMIT DRAWING SHEET 1. | | | | | | --PROVISO-- | | | SBC 2309.6ACCESS TO ATTIC SPACE. | | | TAKING INTO ACCOUNT THE POSITION AND | | | SIZE OF THE NEW AIR HANDLING UNIT AND | | | WATER HEATER, ATTIC ACCESS NOT LESS THAN | | | 22"X36" SHALL BE PROVIDED. |
|