Plan Review Notes
Plan Review Notes For Permit 02010316
Permit Number 02010316
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-24 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SBC* 1707.4PRODUCT APPROVALS.THE
 SUBMITTED PRODUCT APPROVALS DO NOT HAVE
 VALID EXPIRATION DATES.
  
 4) SHEET 2, ROOF FRAMING PLAN.CLARIFY
 DORMER ROOF FRAMING.THE DORMER DETAIL
 SHOWS 2'X8" RAFTERS AT 16 O/C WHILST
 PLAN SHOWS TRUSSES.TRUSS DRAWINGS,
 INCLUDING GIRDER TRUSSES, SHALL BE
 SUBMITTED.
  
 5) SHEET 2, FLOOR FRAMING PLAN.WHERE
 THE EXISTING STAIR OPENING IS TO BE
 FILLED IN, THE PROPOSED 'SIMPSON WS28'
 IS NOT A VALID SIMPSON CONNECTOR
 REFERENCE. PROVIDE CORRECT REFERENCE.
  
 6) SBC 1015.3GUARDRAIL RAILINGS SHALL
 BE SPACED TO REJECT THE PASSAGE OF A 4"
 DIAMETER SPHERE.ADD NOTES TO ENSURE
 COMPLIANCE.
  
 7) SBC 1005.4EMERGENCY EGRESS WINDOW.
 THE SILL HEIGHT OF THE OPENING SHALL NOT
 BE GREATER THAN 44" ABOVE THE FLOOR AND
 THE CLEAR OPENING SHALL BE MINIMUM OF
 24" HIGH AND 20" WIDE.ADD THE REQUIRED
 HEIGHT INFORMATION TO THE PLANS.
  
 8) FL ENERGY CODE 103.0COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499