2002-01-25 00:00:00PERMITS FOR SWIMMING POOLS APPLIED FOR
 ON OR AFTER JANUARY 1, 2002 MUST COMPLY
 WITH SECTION 424 OF THE 2001 FLORIDA
 BUILDING CODE. (FBC)
  
 SHOW THAT THE DESIGN, TOGETHER WITH ANY
 NECESSARY NOTATIONS, ENSURE THAT THE
 CONSTRUCTION AND WORKMANSHIP WILL
 COMPLYWITH ANSI/NSPI-5.SEE FBC
 424.2.6.
  
 PROVIDE THE INFORMATION AND
 SPECIFICATIONS FOR THE PROPOSED HEATER.
  
 NOTE A POOL COVER IS REQUIRED BY SEC
 612.1.ABC.2.3.2 OF THE FLORIDA ENERGY
 CODE.PLEASE INDICATE INTENTION OF
 COMPLIANCE ON PLANS.
  
 SHOW THE METHOD OF ENTRAPMENT AVOIDANCE
 FOR THE VALVED VACUUM FITTING AND THE
 BACK UP SYSTEM IN ACCORDANCE WITH FBC
 424.2.6.6.3.
  
 NOTE THE INSTALLATION DEPTH OF THE
 VACUUM FITTING IN ACCORDANCE WITH FBC
 424.2.6.6.5.
  
 SHOW THE LOCATION OF THE PUMP AND
 EQUIPMENT FOUNDATION.SEE FBC 424.2.22.
  
 CLEARLY SHOW THE METHOD OF SWIMMING
 POOL ENCLOSURE - BARRIER AS PROVIDED
 FOR IN FBC 424.2.17.
  
 EXCERPTS FROM THE FBC ARE ATTACHED FOR Y
 OUR USE.