| Plan Review Notes For Permit 02010255 |
| Permit Number |
02010255 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-08 00:00:00 | ****************UNSAT!****************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING AND RESUBM | | | IT FOR REVIEW: | | | | | | 1)COMPLETE THE AIC RATING TO THELIN SIDE | | | OF THE MAIN DISCONNECTING MEANS. | | | 2)PROVIDE LOAD CALCULATION FOR THE SERVI | | | CE. | | | 3)INCLUDE THE CONDUIT SIZE AND TYPE BETW | | | EEN THE DISCONNECTS. | | | 4)INDICATE THE WIRE SIZE FEEDING THE DIS | | | CONNECT. | | | 5)INDICATE YYPE AND LOCATION OF PANELS. | | | 6)PLEASE SHOW SIZE OF GROUNDING ELECTROD | | | E CONDUCTOR. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN EXAMINER | | | (561)0659-8096 EXT.8392 |
|