| Plan Review Notes For Permit 02010252 |
| Permit Number |
02010252 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-08 00:00:00 | *****************UNSAT!***************** | | | | | | 1)SEE NOTES ON RISER DIAGRAM. | | | 2)PROVIDE AIC RATING TO THE LINE SIDE OF | | | DISCONNECTING MEANS. | | | 3)PROVIDE DRAWINGS FOR ALL UNITS.PLEASE | | | MAKE PLANS MORE LEGIBLE. | | | 4)SHOW SMOKE DETECTORS IN ALL UNITS. | | | 5)LIGHTING AS PER 210-70 | | | 6)PROVIDE PANEL SCHEDULES FOR ALL UNITS. | | | 7)GFI OUTLETS PER 210-52E. | | | 8)BEDROOM OUTLETS PER 210-12(ARC FAULT). | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | (561) 659-8096 EXT.8392 |
|