| Plan Review Notes For Permit 02010242 |
| Permit Number |
02010242 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-08 00:00:00 | 1)PROVIDE AIC RATNG FOR SERVICE | | | 2)PROVIDE LOAD CALCULATION FOR THE | | | SERVICE. | | | 3)PLEASE PROVIDE PANEL SCHEDULES. | | | 4)THE #3 SERVICE CONDUCTORS SUPPLYING | | | THE EXISTING PANELS CANNOT BE PROTECTED | | | BY MORE THAN A 110 AMPERE CIRCUIT | | | BREAKER AS PER 230-46B AND 310-15(B)(6). | | | 5)PLEASE SHOW SERVICE GROUND AND | | | BONDING SIZE AND METHOD ON DRAWING. | | | 6)PLEASE NOTE THAT OUR RECORDS INDICATE | | | THE CONTRACTORS WORKERS COMP INSURANCE | | | AS HAVING EXPIRED 12/31/2001. | | | | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | (561) 659-8096 EXT.8392 |
|