| 2002-02-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR |
| | COMPLIANCE WITH FLORIDA BUILDING CODE |
| | 2001 REQUIREMENTS. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC 1606.1.4EXTERIOR DOOR PRODUCT |
| | APPROVALS.SUBMIT PRODUCT APPROVALS FOR |
| | THE NEW OVERHEAD DOOR AND SLIDING |
| | ENTRANCE DOORS. |
| | |
| | 3) **PROVISO** FBC 1012.4HORIZONTAL |
| | SLIDING DOORS IN A MEANS OF EGRESS.THE |
| | AUTOMATIC SLIDING DOORS (PROJECT MANUAL |
| | SECTION 08462, ITEM 2.02) SHALL COMPLY |
| | WITH THE REQUIREMENTS, STATED IN THE |
| | CODE, FOR SLIDING DOORS IN A MEANS OF |
| | EGRESS. |
| | |
| | 4) FBC 11-4.13.8SLIDING DOOR THRESHOLD |
| | ACCESSIBILITY. ADD A DIMENSION TO |
| | DETAIL A1/8 CONFIRMING THAT THE HEIGHT |
| | OF THE THRESHOLD DOES NOT EXCEED 3/4" |
| | ABOVE FINISHED FLOOR. |
| | |
| | 5) FBC* 104.2EXTENSION OF THE EXISTING |
| | CANOPY.SUBMIT DETAILS TO DESCRIBE THE |
| | EXTENT AND THE MEANS OF SUPPORT FOR THE |
| | CANOPY ABOVE THE NEW OVERHEAD DOOR. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |