| 2002-02-05 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE SOIL REPORT PER SEC. 1804.2.2 |
| | OF CITY AMENDMENTS TO 1997 SBC. |
| | |
| | 3) GENERAL NOTE #9 ON SHEET C-1 SITES |
| | THE WRONG EDITION OF THE FLORIDA ENERGY |
| | CODE. CORRECT EDITION IS THE 1997. |
| | |
| | 4) ON SHEET C-1 THE NOTE UNDER LOAD |
| | SCHEDULE INCORRECTLY REFERENCES THE 1999 |
| | STANDARD BUILDING CODE. THE 1997 SBC IS |
| | THE CORRECT EDITION. |
| | |
| | 5) SAFETY GLASS IS REQUIRED IN THE |
| | WINDOW OF BATH #3 PER 97 SBC 2405.2. |
| | |
| | 6)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SINGLE HUNG WINDOWS |
| | - ARCHED FIXED GLASS WINDOWS |
| | - RECTANGULAR F.G. WINDOWS |
| | - STRUCTURAL MULLIONS |
| | |
| | 7) THE 1-1/2" FASTNERS SPECIFIED FOR |
| | ATTACHING THE 2X4 P.T. BUCKS ON THE DOOR |
| | JAMB DETAIL(SHEET A-4)IS NOT SUFFICIENT. |
| | PLEASE CORRECT. |
| | |
| | 8) THE TRUSS CONNECTOR SCHEDULE ON SHEET |
| | A-6 SPECIFIES SEMCO CONNECTORS. SEMCO |
| | HAS BEEN PURCHASED BY USP AND THE |
| | TAPR 220 IS LISTED IN THEIR CATALOG WITH |
| | WITH A MAXIMUM UPLIFT OF 1485#. PLEASE |
| | REVISE THE SCHEDULE. |
| | |
| | 9) BRACING NOTE #7 ON SHEET A-6 STATES |
| | THAT IT MEETS THE REQUIREMENTS OF |
| | CHAPTER 23 AND SECTION 2906.17 OF THE |
| | S.F.B.C. ARE YOU REFERING TO CHAPTER 23 |
| | OF THE S.B.C.? DELETE THE REFERENCE TO |
| | THE SOUTH FLORIDA BUILDING CODE. |
| | |
| | 10) THE SITE SPECIFIC PRODUCT APPROVAL |
| | FORMS ARE REQUIRED TO BE SIGNED AND |
| | SEALED BY THE DESIGNER OF RECORD, IN |
| | ADDITION TO THE ENGINEER. |
| | |
| | 11) THE L-2 LINTEL OVER THE SLIDING |
| | GLASS DOOR AT THE LIVING ROOM IS |
| | REQUIRED TO HAVE A MINIMUM END BEARING |
| | OF 4" PER 2101.3.1. HOW IS THIS BEING |
| | ACCOMPLISHED AT MASONRY COLUMN C-7? |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |