| Notes |
| Date |
Text |
| 2002-02-04 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE ELEC RISER FOR EAST END | | | OF PARK ON E-10.PLEASE CLARIFY GROUND | | | FOR TRANSFORMER?250 | | | | | | 2)NOTE: PLEASE SEE E-11, PLEASE NOTE THE | | | NEW 300KVA TRANSFORMER NEEDS TO BE | | | SHOWN ON LINE DIAGRAM. PLEASE CLARIFY | | | EQUIPMENT GRPUNDS TO AND FROM?? | | | ALSO GROUNDING OF TRANSFORMER.250 | | | | | | 3)NOTE: PLEASE SEE ELEC POWER DIST AT | | | WEST END OF PARK. PLEASE CLARIFY | | | GROUND FOR THE TRANSFOMER. | | | PLEASE CLARIFY WHICH PART OF THIS DIST | | | SYSTEM IS FPL/ OR OTHER.215-5 | | | | | | 4)NOTE: PLEASE LABEL ALL PANEL SCHEDUE | | | TO CORRELATE WITH RISER DIAGRAM.215-5 | | | | | | 5)NOTE: PLEASE SHOW ALL CONTINUOUD LOADS | | | AT 125%.215-2/3,230-42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|