| 2002-01-11 00:00:00 | ********************DENIED************** |
| | |
| | 1.PLAN SHEET M1.1 INDICATE AIR FROM |
| | THE MALE AND FEMALE BATHROOMS IS |
| | TO BE TRANSFERED INTO THE COMMON |
| | AREAS, AS PER 1997 SMC 503.3.1 - |
| | AIR EXHAUSTED FROM BATH TOILET, |
| | URINAL, LAVATORY, LOCKER, COAT ROOM |
| | OR SIMILAR ROOMS SHALL NOT BE |
| | RECIRCULATED. |
| | |
| | 2.PLEASE NOTE FIRE DEPARTMENT COMMENT |
| | #1,SHOULD THESE ROOMS HAVE A FIRE |
| | SEPARATION, FIRE DAMPERS WILL BE |
| | REQUIRED.INDICATE LOCATION OF |
| | FIRE DAMPERS AND INSTALLATION DETAIL |
| | ON PLAN. |
| | |
| | 3.WHAT IS THE UTILITY ROOM USED FOR? |
| | |
| | 4.AS PER 1997 SMC 406.1, FAN SHUTDOWN |
| | BY DUCT SMOKE DETECTOR IN THE RETURN |
| | AIRSTREAM PROIR TO ANY EXHAUSTING |
| | FROM THE BUILDING OR MIXING WITH |
| | FRESH AIR MAKEUP. |
| | |
| | 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | WITH NOTIFICATION TO ALARM/STROBE IN |
| | NORMALLY OCCUPIED AREAS. NFPA 90A |
| | 4-4.4.3. |
| | |
| | 6.PLEASE INDICATE SIZE AND TERMINATION |
| | OF THE CONDENSATE.UNITS LARGER |
| | THAN 3 TON SHALL TERMINATE INTO: |
| | |
| | 1.AN APPROVED DRY WELL |
| | 2.TO STORM DRAIN |
| | |