| Plan Review Notes For Permit 02010047 |
| Permit Number |
02010047 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-16 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY | | | AND A SITE PLAN WITH DIMENSIONS LOCATING | | | THE PROPOSED BUILDING ON THE PROPERTY. | | | INCLUDE TOPOGRAPHIC INFORMATION SO | | | THATCOMPLIANCE WITH HANDICAP SITE | | | ACCESSIBILTY MAY BE DETERMINED. | | | | | | PROVIDE PRODUCT TEST REPORTS AND OR | | | NOTICE OF ACCEPTANCE DATA FOR THE | | | DOORS, WINDOWS AND ROOF COVERING TO BE | | | USED. | | | | | | SHOW THE METHOD OF HURRICANE MISSILE | | | IMPACT RESISTANT FOR THE EXTERIOR | | | GLAZED PORTIONS OF THE BUILDING. | | | | | | SHOW THE SPECIFIC CODE AND DESIGNS | | | STANDARDS USED FOR THIS BUILDING. | | | | | | THE ROOF NOTES ON SHEET S3 DO NOT | | | DEFINETHE SIZE OR LOCATION OF THE 3 | | | ZONES FOR WIND PRESSURE.INCLUDE THE | | | PRESSURE ZONES FOR COMPONENTS AND | | | CLADDING ON THE WALLS ALSO. | | | | | | PLEASE PROVIDE STRUCTURAL CALCULATIONS | | | FOR THE 2X4 PURLINS ON THE ROOF | | | DEMONSTRATING THEIR ABILITY TO RESIST | | | UPLIFT THE DECLARED UPLIFT PRESSURES. |
|