Plan Review Notes
Plan Review Notes For Permit 01121783
Permit Number 01121783
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-02 00:00:00**************UNSATISFACTORY!***********
 1)PROVIDE AIC RATINGS AS PER NFPA-70,ART
 CLE 110-9 & 110-10.
 2)PROVIDEICAL LOAD CALLCULATIONS F
 R THE SERVIEBRANCH CIRCUITS AND FEEDERS.
 ***************UNSAT!*******************
 1)PROVIDE AIC RATINGS AS PER
 NFPA-70,ARTICLES 110-9 & 110-10
 2)PROVIDE ELECTRICAL LOAD CALCULATIONS
 FOR THE SERVICE,BRANCH CIRCUITS AND
 FEEDERS.
 3)PROVIDE METER ENCLOSURE TYPE AND
 AMPERAGE ON RESUBMITTALS.
 4)PLEASE SHOW PANEL TYPE,SIZE AND NUMBER
 OF CIRCUITS.
 5)PLEASE SUBMIT PANEL SCHEDULE.
 6)SHOW ALL CONDUIT SIZE AND TYPE FOR
 SERVICE AND RELATED EQUIPMENT.
 7)PROVIDE ALL CONDUCTOR SIZE,TYPE AND
 NUMBER OF SAME IN NEW OR ADDED CONDUIT.
 8)SHOW ALL GROUNDING AS PER NEC.
 9)PLEASE DRAW RESUBMITTALS TO BE
 LEGIBLE10)SHOW LOCATION OF GFI AT REAR
 OF THE HOUSE AS PER 210-52E.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 (561) 659-8096 EXT.8392