| Plan Review Notes For Permit 01121770 |
| Permit Number |
01121770 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-08-08 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE REVISE TO SHOW CODE COMPLIANCE | | | FOR THE FOLLOWING. | | | | | | 1} THE GEC FOR A 400 AMP SERVICE IS 1/0 | | | PER 210.66 | | | | | | 2} THE 225 OCP FOR PANELS "A" & "B" IS | | | INCORRECT FOR 2/0 CONDUCTORS,THESE | | | FEEDERS SHOULD BE 3/0 FOR 225 AMPS PER | | | 310.15(B)(6). | | | | | | SHOW CORRECT PANEL "C" & "D" FEEDS, | | | RISER AND PANEL SCHEDULE DO NOT | | | CORRELATE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|