Plan Review Notes
Plan Review Notes For Permit 01121770
Permit Number 01121770
Review Stop B
Sequence Number 3
Notes
Date Text
2002-04-02 00:00:00APPROVED WITH PROVISO:
 1-SITE SPECIFIC PRODUCT APPROVAL FOR
 ENTRY DOORS WITH SIDELITES. ENGINEER
 NEEDS TO CAREFULLY REVIEW CONSTRUCTION
 DRAWINGS TO REVISE THE FOLLOWING:
 A)SEE BUILDING CODE USED BY ARCHITECT TO
 DESIGN THE STRUCTURE.
 B)REVISE THE MEAN ROOF HEIGHT FOR BLDG.
 SEE EXTERIOR ELEVATIONS.
 C)STRUCTURE TO RECEIVE ENTRY DOORS
 ASEMBLY IS NOT CONCRETE COLUMNS, BUT
 FILLED CONCRETE BLOCK COLUMNS. SEE
 ARCHITECT'S PLANS.
 2-ARCHITECT TO PROVIDE CERTIFICATION
 STATING THAT HE REVIEW THE SITE
 SPECIFIC ENGINEERING FOR THE ENTRY
 ASSEMBLY AND WILL BE OK FOR HIS BLDG
 AND THAT HIS STRUCTURE WILL RESIST THE
 LOADS APPLIED BY THIS ASSEMBLY.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 NOTES:
 A)SEE PLANS FOR AREAS TO RECEIVE PANELS.
 B)SEE TABLE 1 ON STORM SHUTTERS DWGS FOR
 MAX. PANEL SPAN AND OPENINGS TO BE
 INSTALLED ON. IT DOESN'T WORK.
 C)CHECK ANCHOR TYPE AND SPACING TO BE
 USED ACCORDING TO DESIGN PRESSURES,
 MEAN ROOF HEIGHT, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 BLOCK OR CONCRETE).
 4-SITE SPECIFIC ENGINEERING FOR BUTT
 GLAZING ASSEMBLIES:
 A)ENGINEER TO PROVIDE COMPLETE
 ENGINEERING CALCULATIONS FOR SITE
 SPECIFIC APPLICATIONS (THIS IS NOT AN
 APPROVED PRODUCT APPROVAL, THEREFORE
 COMPLETE SITE SPECIFIC ANALYSIS IS
 REQUIRED) USING THE BUILDING CODE FOR
 WHICH BUILDING WAS DESIGNED.
 B)PRODUCT APPROVAL SUBMITTED FOR SERIES
 4500 STOREFRONT SYSTEM IS TO BE USED
 WITH MULLIONS, NOT BUTT GLAZING. SEE
 PRODUCT APPROVAL DRAWINGS.
 C)ARCHITECT TO PROVIDE CERTIFICATION AS
 DONE FOR ENTRY DOORS ASSEMBLY.
  
 NOTE: REMEMBER THAT ALL DOCUMENTS THAT
 ARE SUBMITTED FOR PUBLIC RECORDS BY
 ARCHITECTS/ENGINEERS NEED TO BE SIGNED,
 SEALED & DATED AND PROFESSIONALS NEED TO
 PROVIDE ALL THEIR INFORMATION AS REQ'D
 BY CHAPTER 471/481 OF FLORIDA STATUTES.
  
 5-PROVIDE COMPLETE UL LISTING & SPECS
 FOR FIREPLACE AND BBQ PRIOR TO
 INSTALLATION (TWO COPIES OF EACH).
 6-ARCHITECT TO PROVIDE DETAIL/SPECS FOR
 2X STRUCTURAL BUCK DETAILS AS REQUIRED
 FOR SWING DOORS AND STOREFRONT SYSTEM.
 7-PROVIDE PRODUCT APPROVAL OR SITE
 SPECIFIC ENGINEERING FOR FRENCH DOOR
 WITH TRANSOM ABOVE SINGLE ASSEMBLY W/
 SIZES & STRUCTURE TYPE ATTACHED TO AS
 SHOWN ON EXTERIOR ELEVATIONS.
 **ARCHITECT TO PROVIDE CERTIFICATION AS
 REQUESTED ON PREVIOUS ITEMS.