| Plan Review Notes For Permit 01121760 |
| Permit Number |
01121760 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-18 00:00:00 | ****************UNSAT!****************** | | | | | | PLEASE REVISE AND RESUBMIT WITH THE | | | FOLLOWING: | | | | | | 1) PROVIDE AN A.I.C. RATING TO THE LOAD | | | SIDE OF THE FIRST MEANS OF DISCONNECT. | | | | | | 2) INDICATE GROUNDING METHOD BEING | | | USED,INCLUDE 250-50(A) & (C). | | | | | | 3) 250-52 (D) INSTALL GFI IN BATH. | | | | | | 4) COMPLY WITH 250-52(A)(2)(A),IN | | | BEDROOMS AND MASTER SUITE,(SEE PLANS). | | | | | | 5) WATER HEATER TO COMPLY WITH 422-16(A) | | | ALSO NOTE 422-33. | | | | | | 6) ENGINEER PLEASE NOTE AND COMPLYWITH | | | F.S. 61G15-23.002, ALL SHEETS. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT.8392 |
|