| 2002-01-31 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FL ENERGY CODE 103.1.2BEFORE A |
| | BUILDING PERMIT CAN BE ISSUED, THE |
| | SUBMITTED ENERGY CODE COMPLIANCE FORMS |
| | SHALL BE SIGNED BY THE BUILDING OWNER, |
| | THE OWNER'S ARCHITECT OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY |
| | THE OWNER. |
| | |
| | 4) SBC* 104.1.1A SEPARATE ROOFING |
| | PERMIT APPLICATION IS REQUIRED. |
| | |
| | 5) ROOF TRUSS DRAWINGS SHALL BE |
| | SUBMITTED. |
| | |
| | 6) SBC* 104.2.2PREFABRICATED ROYALL |
| | WALL PANELS.ENGINEERING DETAILS, |
| | INCLUDING ANCHORAGE TO THE FOUNDATIONS, |
| | SIGNED AND SEALED BY THE ENGINEER, SHALL |
| | BE SUBMITTED.ASSOCIATED WINDOW/DOOR |
| | HEADER AND FASTENING DETAILS ARE ALSO |
| | REQUIRED. |
| | |
| | 7) SBC TABLE 600THE "LEFT ELEVATION" |
| | (EAST ELEVATION) SETBACK IS 8'6".FOR |
| | TYPE V CONSTRUCTION AND A SETBACK |
| | BETWEEN 3' AND 10', TABLE 600 ALLOWS FOR |
| | 10% OF THE WALL AREA TO BE UNPROTECTED |
| | OPENINGS.THE PROPOSED AREA OF WINDOWS |
| | IN THIS WALL EXCEEDS THE ALLOWABLE |
| | PERCENTAGE.ADJUST THE SETBACK TO AT |
| | LEAST 10' OR AMEND THE WINDOW AREA TO |
| | COMPLY. |
| | |
| | 8) SBC 1804.1.3THE PLANS SHALL BE |
| | AMENDED TO SHOW THE BASE LEVEL FOR THE |
| | EXTERIOR WALL FOUNDATIONS AT LEAST 12" |
| | BELOW FINISH GRADE. |
| | |
| | 9) SBC* 1606.4THE PLANS SHALL MAKE |
| | REFERENCE TO THE REQUIREMENT FOR STORM |
| | SHUTTERS ON ALL WINDOWS AND DOORS EXCEPT |
| | THE FRONT ENTRANCE DOOR. |
| | |
| | 10) SBC 2405.2.1THE GLAZING IN THE |
| | PATIO DOORS AND THE DOOR TO THE PATIO IS |
| | IN A "HAZARDOUS LOCATION".PROVIDE |
| | DETAILS TO SHOW COMPLIANCE WITH THE |
| | REQUIREMENT FOR 'SAFETY GLASS'. |
| | |
| | 11) SBC 2309.6THE PLANS SHALL BE |
| | AMENDED TO SHOW AN INTERIOR ATTIC ACCESS |
| | OPENING NOT LESS THAN 22"X36". |
| | |
| | 12) SBC 2309.7ATTIC SPACE VENTILATION |
| | SHALL BE PROVIDED IN COMPLIANCE WITH THE |
| | AREA AND LOCATION REQUIREMENTS. |
| | |
| | 13) TYPICAL HIP TRUSS CONNECTION TO WALL |
| | THE TYPICAL WALL SECTION SHOWS SIMPSON |
| | LGT2 CONNECTORS WITH 14-10D NAILS INTO |
| | THE HIP TRUSS.THIS WOULD RESULT IN |
| | REDUCED LOAD CAPACITY COMPARED TO THE |
| | SIMPSON RECOMMENDATION FOR 14-16D |
| | FASTENERS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |