| Plan Review Notes For Permit 01121737 |
| Permit Number |
01121737 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-25 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ONLY THE | | | ELECTRICAL RISER DIAGRAM IS STILL | | | SUBMITTED? PLEASE CLARIFY WHERE SHELL | | | ELECTRICAL IS SHOWN? | | | | | | 2)NOTE: PLEASE NOTE THAT NOTE#1 FROM | | | FIRST REVIEW STILL NEEDS TO BE ADDRESSED | | | PLEASE NOTE LOAD CALCUALTIONS NEED TO | | | BE SHOWN. WATTS PER SQ FT ETC. | | | NEC ART 220. | | | | | | PLEASE NOTE FIRE REVIEW NOTES FOR EM LTS | | | AND EXIT LTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|