| 2002-01-07 00:00:00 | 1) PLEASE BE ADVISED THAT THE BUILDING | | | IS LOCATED WITHIN THE CITY FIRE LIMITS. | | | CERTAIN RESTRICTIONS APPLY. | | | 2) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 3) NO INDICATIONS ON PLANS REGARDING | | | THE RATINGS ON THE PROPOSED TENANT WALLS | | | 4) NO ILLUMINATED EXIT SIGNS OR | | | EMERGENCY LIGHTING SHOWN ON THE PLANS. | | | 5) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION ON PLANS FOR THE WALLS | | | AND CEILINGS. | | | 6) THE PLANS INDICATE AN EXISTING FIRE | | | SPRINKLER RISER, HOWEVER NO FIRE | | | SPRINKLER WERE SUBMITTED WITH THE | | | DRAWINGS. IT IS BELIEVED THAT THE | | | FIRE SPRINKLER SYSTEM IS OF AN OLDER | | | TYPE AND THE PRESENT CONDITION OF IT | | | IS UNKNOWN. | | | 7) NO EXIT DOORS SHOWN FROM TENANT | | | SPACE. | | | 8) PLEASE EXPLAIN HOW EXITING OCCURS | | | FROM THE BUILDING. PLEASE EXPLAIN | | | RATIONALE FOR EXITING. | | | 9) WHAT WILL THE CURVED STAIR TO BE | | | USED FOR. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|