2002-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE LOAD CALACULATIONS
 NEED TO BE SHOWN. 215-5,220-3,220-10,
 220-11,220-13 ETC. PLEASE ALSO NOTE
 THAT ALL CONTINUOUS LOADS NEED TO BE
 SHOWN AT 125%. 230-42,215-3.
  
 2)NOTE: PLEASE NOTE THAT TOTAL EXCEEDS
 RATING OF SERIVCE ENTRANCE CONDUCTORS
 310-16.
 ALSO NOTE OCP IS NOT LARGE ENOUGH FOR
 LOAD SHOWN.
  
 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING BETWEEN DISCONNECT AND
 UNIT PANELS.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5)NOTE: PLEASE PROVIDE SIZING OF GUTTER.
 374
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  