2002-01-15 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01121737
 711 N DIXIE
 CONT: GSP & ASSOCIATES
 TEL: (561) 697-8444
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
 1997 EDITION
  
 1)- SBC* 104.2.2 ADDITONAL INFORMATION
 REQUIRED. BETWEEN THE SITE PLAN & ARCH.
 PLANS PATH OF TRAVEL FOR HANDICAPPED IS
 UNCLEAR FOR ENTRY RAMP.
  
 2)- PLEASE INDICATE WHAT TYPE OF BUILD-
 ING DESIGN WAS USED IN THE DESIGN?
 PLANS INDICATE A EXISTING FIRE RISER, IS
 THIS TO BE CONSIDERED A FIRE SPRINKLERED
 BUILDING? IF SO,ADDITIONAL INFORMATIOIN
 WILL BE REQUIRED TO DO A COMPETENT PLAN
 REVIEW. THIS PLAN REVIEW WAS COMPLETED
 AS A WORSE CASE, NO FIRE SPRINKLERS
 SINCE THE REQUIRED INFORMATION WAS LACK-
 ING.
  
 3)- SBC (FIRE DISTRICT) 102.1 TYPES OF
 CONSTRUCTION PRMITTED. TYPE I,II,III,
 IV OR V ARE PERMITTED IN FIRE DISTRICT.
  
 4)- BALCONY INDICATES USE OF WOOD ON THE
 EXTERIOR WALLS.
  
 5)-SBC FI02.2.5 ALL WALLS, FLOORS,
 ROOFS, & THEIR SUPPORTING STRUCTURAL
 MEMBERS SHALL PROVIDE NOT LESS THAN
 1-HR FIRE RESISTANCE.
  
 6)- SBC TABLE 600 INDICATE COMPLIANCE
 WITH TYPE V BUILDING 0'-3' FROM PROPERTY
 LINE 3 HR EXTERIOR WALLS.
  
 7)- SURVEY INDICATES THE FRONT ENTRY
 PROJECTING 1'-0" INTO THE PUBLIC PROPER-
 TY AT GRADE ?
  
 8)- BALCONY CORBELS, WHAT TYPE OF MATER-
 IAL, HOW WILL IT BE ATTACHED?
  
 9)- F 102.2.7 ARCH. TRIM APPROVED NON-
 COMBUSTIBLE TRIM SHOW COMPLIANCE REPORT
 FOR NONCOMBUSTIBLES, (EXPANDED POLYSTI-
 RENE SYSTEMS).
  
 10)- ENERGY CALS W/ MANUAL "J"
  
 11)- SHEET A101, SHOW DOORWAYS INTO
 TENANT SPACE. SBC1001.1.2.IN EVERY BUILD
 ING HEREAFTER ERECTED, MEANS OF EGRESS
 SHALL COMPLY WITH THE MINIMUM REQUIRE-
 MENTS OF THIS CHAPTER. THE PLANS DO NOT
 INDICATE EGRESS FROM TENANT SPACE OR
 COMMON ELEMENTS AS RESTROOMS.
  
 12)- SECOND FLOOR EGRESS, SBC 1020.1-
 SINGLE EGRESS REQUIREMENTS > 3500 SQ FT,
 DO NOT MEET REQUIREMENTS, 1004.2.2 REQUI
 RES A MINIMUM OF 2 MEANS OF EGRESS ARE
 REQUIRED.
  
 13)- SHEET 101/201 SBC 1004.1.4. WHERE
 2 OR MORE EXITS OR EXIT ACCESS DOORS
 SHALL BE PLACED A DISTANCE APART EQUAL
 TO NOT LESS THAN ONE HALF OF THE LENGTH
 OF THE MAXIMUM OVERALL DIAGONAL DIMEN-
 SION OF THE BUILDING OR AREA TO BE
 SERVED.
  
 14)- EXITS, SPIRAL STAIRS, SBC 1006.1.1.
 EXIT STAIRWAYS BETWEEN FLOORS SHALL BE
 ENCLOSED IN OR SEPERATED BY FIRE RESIS-
 TANT CONSTRUCTION IN ACCORDANCE WITH
 705.2 & TABLE 705.1.2.PRPOTECTION OF
 FLOOR OPENINGS.
  
 15)- SBC 704.2.4. EXIT ACCESS CORRIDORS:
 FIRE EXIT RATINGS SHALL BE IN ACCORDANCE
 WITH TABLE 704.2.3.2.
  
 16)- SBC 705.1.1.FIRE RATED ASSEMBLIES
 SHOW COMPLIANCE EITHER UL LISTING OR GYP
 SUM ASSOC NUMBER.
  
 17)- SBC 705.5.1.2. FIRESTOP SYSTEMS,
 LIST PRODUCTS ,CUT SHEETS.
  
 18)- SPIRAL STAIRS: SBC SHOW HOW ONCE
 YOU LEAVE THE STAIR ENCLOSURE FOR SPIRAL
 STAIRS COMPLIANCE FOR EXIT PASSAGEWAYS
 SBC 1010.3.
  
 19)- 1004.3.1 ACCESSIBLE MEANS OF EGRESS
 WHERE MORE THAN 1 MEANS OF EGRESS IS RE-
 QUIRED FROM ANY REQUIRED ACCESSIBLE
 SPACE, EACH ACCESSIBLE PORTION OF SPACE
 SHALL BE SERVED BY NOT LESS THAN 2A
 CCESSIBLE MEANS OF EGRESS.
 1004.3.2.1. TO BE AN ACCESSIBLE MEANS OF
 EGRESS SHALL HAVE A CLEAR WIDTH OF 48"
 BETWEEN THE HANDRAILS AND INCORPARATE
 AN AREA OF REFUGE WITHIN AN ENLARGED
 STORY LEVEL LANDING OR SHALL BE ACCESSED
 FROM EITHER AN AREA OF REFUGE COMPLYING
 WITH 1004.3.5 OR A HORIZONTAL EXIT.
  
 20)- SHEET A.104 SHOW COMPLIANCE WITH
 SECTION 1007.5.5.12" HANDRAIL EXTENTIONS
  
 21)- SHEET A-105 SEC 2: GUARDRAILS SEE
 1015.3 FOR 4" SPHERE (BALCONY), ALSO
 SHEET A104 SEC BB GAURDRAIL 2" SPHERE
 AT NEW GUARDRAIL.
  
 22)-SBC 1606.2.6.2 COMPONENTS & CLADDING
 PROVIDE (2 COPIES) OF PRODUCT APPROVAL
 REPORTS FOR ALL GLAZED OPENINGS, WINDOWS
 DOORS & SKYLIGHTS. DOORS WITH NO GLAZING
 (EXTERIOR) SHALL ALSO BE REQUIRED TO SUB
 MIT PRODUCT TESTING REPORTS.
  
 23)- MISSING WINDOW & DOOR BUCK ATTACH-
 MENT.
  
 24)- PROVIDE INFORMATION ON NEW ROOF
 ACCESS ?
  
 25)- UNCLEAR AS TO WHAT IS GOING TO
 HAPPEN AT EXISTING SKYLIGHT? IS THE SKY-
 LIGHT BEING USED FOR THIS PURPOSE?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412