| Plan Review Notes For Permit 01121731 |
| Permit Number |
01121731 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-02 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SHT 1 BATHROOM DOOR SHALL NOT SWING | | | INTO CLEAR FLOOR SPACE OR UNOBSTRUCTED | | | TURNING RADIUS. SEC 4.22.2 | | | 2) SHT 1 W/C SHALL BE 1'6" TO CENTER OFF | | | WALL NOT 2'2" AS SHOWN. | | | 3) SHT 1 SHOW DETAIL FOR HDCP FIXTURES | | | W/C AND LAV PER SECS 4.16, 4.16.2, | | | 4.16.3, 4.16.5 AND 4.19, 4.19.2, 4.19.3, | | | 4.19.4, 4.19.5 | | | 4) SHT 1 TABLE 407 REQUIRES A DRINKING | | | FOUNTAIN. | | | 5) SHT 1 SANT RISER SHOWS A DRY HORIZON- | | | TAL VENT. PER SEC 906.2.1 THIS IS NOT | | | APPROVED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|