| 2002-01-07 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS FOR | | | # 01090788 SHOW A HEAT PUMP AT 11KW | | | BEING IN LOAD CALCULATIONS. | | | | | | 2)NOTE: PLEASE NOTE THAT WIRING DIAGRAM | | | ON THESE PLANS DO NOT INCLUDE ANY | | | HEAT PUMP OR ASSC. WIRING? | | | PLEASE SHOW, INCLUDE, WIRE SIZE, CONDUIT | | | ETC. PLEASE CLARIFY HEAT PUMP SIZE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|