Plan Review Notes
Plan Review Notes For Permit 01121693
Permit Number 01121693
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-01-15 00:00:001) SITE PLAN FOR THE BUILDING SHOULD
 PROVIDE INFORMATION ON FIRE HYDRANT
 LOCATIONS, SIZE AND LOCATIONS OF FIRE
 MAINS, ETC.
 2) HOW IS FIRE RESCUE EXPECTED TO ENTER
 THE COMPLEX. WILL THE GUARD HOUSE
 BE STAFFED FULL OR PART TIME OR WILL
 THEIR BE CERTAIN TIMES THAT IT WILL
 BE STAFFED.
 3) WHERE ARE THE ARCHITECTURAL PLANS FOR
 THE ADULT LIVING FACILITY.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR GENERATOR INSTALLATION.
 5) DUCT SMOKE DETECTORS WHEN ACTIVATED
 SHALL CAUSE THE FIRE ALARM SYSTEM TO
 ACTIVATE.
 6) PLEASE EXPLAIN DRY SYSTEM NOTES ON
 PAGE E6.6.
 7) KITCHEN FIRE SUPPRESSION NOTES ON
 E6.4 NEEDS TO IDENTIFY THAT WHEN THE
 HOOD SYSTEM ACTIVATES, THE EXHAUST
 FAN IS TO RUN AND THE MAKE-UP AIR
 SHUT DOWN.
 8) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED FOR ADULT LIVING
 FACILITY.
 9) PLEASE CORRELATE THE PLANS THAT
 WERE SUBMITTED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910