| Plan Review Notes For Permit 01121693 |
| Permit Number |
01121693 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-15 00:00:00 | 1) SITE PLAN FOR THE BUILDING SHOULD | | | PROVIDE INFORMATION ON FIRE HYDRANT | | | LOCATIONS, SIZE AND LOCATIONS OF FIRE | | | MAINS, ETC. | | | 2) HOW IS FIRE RESCUE EXPECTED TO ENTER | | | THE COMPLEX. WILL THE GUARD HOUSE | | | BE STAFFED FULL OR PART TIME OR WILL | | | THEIR BE CERTAIN TIMES THAT IT WILL | | | BE STAFFED. | | | 3) WHERE ARE THE ARCHITECTURAL PLANS FOR | | | THE ADULT LIVING FACILITY. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR GENERATOR INSTALLATION. | | | 5) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL CAUSE THE FIRE ALARM SYSTEM TO | | | ACTIVATE. | | | 6) PLEASE EXPLAIN DRY SYSTEM NOTES ON | | | PAGE E6.6. | | | 7) KITCHEN FIRE SUPPRESSION NOTES ON | | | E6.4 NEEDS TO IDENTIFY THAT WHEN THE | | | HOOD SYSTEM ACTIVATES, THE EXHAUST | | | FAN IS TO RUN AND THE MAKE-UP AIR | | | SHUT DOWN. | | | 8) NO FIRE SPRINKLER OR HYDRAULIC | | | CALCULATIONS PROVIDED FOR ADULT LIVING | | | FACILITY. | | | 9) PLEASE CORRELATE THE PLANS THAT | | | WERE SUBMITTED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|