Plan Review Notes
Plan Review Notes For Permit 01121693
Permit Number 01121693
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-28 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE E2.1 SOME NOTES DO NOT
 CORRELATE WITH PLANS. SEE #11, TWO #17`S
 #10?
  
 2)NOTE: PLEASE SHOW GFI LOCATIONS FOR
 A/C COND UNITS REQ`D PER 210-63 AND
 309.2 OF THE MECH CODE. IN A READILY
 ACCESS. PLEASE SHOW LOCATIIONS ON E4.5
 ROOF TOP ALSO.
  
 3)NOTE: PLEASE SEE MISSING OUTLETS PER
 2' OF WALL IN UNITS. 210-52
  
 4)NOTE: PLEASE NOTE THAT LOAD ON PANELS
 P1EA,P1EB EXCEED 150AMPS.
  
 5)NOTE: PLEASE SEE LOADS FOR PANELS
 P2EC,ED,EE EXCEEDS RATING OF EQUIPMENT.
 PLEASE NOTE CONDUCTOR SIZE WON'T BE
 LARGE ENOUGH.
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 CLARIFY IF COMPLETE FIRE ALARM WILL
 CARRY SD`S.?
  
 7)NOTE: PLEASE NOTE SHUNT TRIPS SHOWN
 ON EDP NEED TO BE CLARIFIED. SEE
 NEC 230-76 AND 230-79.
  
 8)NOTE: PLEASE NOTE/ PROVIDE MORE DETAIL
 FOR TYPES OF MOTORS FOR ELEVATORS AND
 TYPE OF BRKR OCP.
 430-148(TABLES)
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR'
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-65-8096 EXT8372