| Date |
Text |
| 2002-01-28 00:00:00 | **************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE E2.1 SOME NOTES DO NOT |
| | CORRELATE WITH PLANS. SEE #11, TWO #17`S |
| | #10? |
| | |
| | 2)NOTE: PLEASE SHOW GFI LOCATIONS FOR |
| | A/C COND UNITS REQ`D PER 210-63 AND |
| | 309.2 OF THE MECH CODE. IN A READILY |
| | ACCESS. PLEASE SHOW LOCATIIONS ON E4.5 |
| | ROOF TOP ALSO. |
| | |
| | 3)NOTE: PLEASE SEE MISSING OUTLETS PER |
| | 2' OF WALL IN UNITS. 210-52 |
| | |
| | 4)NOTE: PLEASE NOTE THAT LOAD ON PANELS |
| | P1EA,P1EB EXCEED 150AMPS. |
| | |
| | 5)NOTE: PLEASE SEE LOADS FOR PANELS |
| | P2EC,ED,EE EXCEEDS RATING OF EQUIPMENT. |
| | PLEASE NOTE CONDUCTOR SIZE WON'T BE |
| | LARGE ENOUGH. |
| | |
| | 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | CLARIFY IF COMPLETE FIRE ALARM WILL |
| | CARRY SD`S.? |
| | |
| | 7)NOTE: PLEASE NOTE SHUNT TRIPS SHOWN |
| | ON EDP NEED TO BE CLARIFIED. SEE |
| | NEC 230-76 AND 230-79. |
| | |
| | 8)NOTE: PLEASE NOTE/ PROVIDE MORE DETAIL |
| | FOR TYPES OF MOTORS FOR ELEVATORS AND |
| | TYPE OF BRKR OCP. |
| | 430-148(TABLES) |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR' |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-65-8096 EXT8372 |