| 2002-01-26 00:00:00 | DENIED |
| | REFERENCE: SPC-94-FACBC-97 |
| | |
| | 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN- |
| | ESS REGULATION HOTEL & RESTURANT DIV. |
| | FOR REVIEW AND COMMENTS BEFORE RESUBMIT- |
| | ING FOR PLAN REVIEW. |
| | 2) SHT P2, PLEASE CONTACT RODNEY COMPO |
| | ENVIRONMENTAL COMPLIANCE (561) 837-4074 |
| | FOR GREASE TRAP SIZE. WASTE ORD. #2938- |
| | 96. SUBMIT REVIEW LETTER BEFORE RESUBMIT |
| | ING FOR PLAN REVIEW, |
| | 3) PLEASE SUBMIT CALCULATIONS FOR MINIM- |
| | UM FACILITIES PER SPC TABLE 407 AND SEC |
| | 407.1.3. SHOW DEDUCTED AREAS. |
| | 4) PLEASE PROVIDE A WATER RISER DIAGRAM. |
| | SHOW PIPE SIZES, WATER HAMMER ARRESTORS |
| | LOCATION OF BACKFLOW PREVENTERS ECT. |
| | REDUCED PRESSURE BACKFLOW REQUIRED ON |
| | WATER SERVICE TO CLUBHOUSE. |
| | 5) STORM RISER DIAGRAM REQUIRED. INCLUDE |
| | PIPE SIZES AND SQ FT ADDED FROM EACH |
| | DOWNSPOUT AND TRENCH DRAIN. |
| | 6) SHT A2.1 & SHT P2, STAFF TOILET ROOM |
| | #149B, DOOR SHALL NOT SWING INTO CLEAR |
| | FLOOR SPACE OF LAV. FACBC SEC 4.22.2 |
| | 7) SHT A5.4 DETAIL #8 STAFF SINK TO |
| | COMPLY WITH FACBC SEC 4.24. SHOW DETAILS |
| | FOR ALL SUBSECTIONS. |
| | 8) SHT A5.3 RM #129 DETAIL #1 HAIRCARE |
| | VACUUM BREAKER REQUIRED ON WATER SUPPLY |
| | 6" ABOVE FLOOD RIM LEVEL. |
| | 9) SHT A2.1 & P1 FOUNTAIN, PLUMBING |
| | CONTRACTOR TO SUPPLY VALVE AND BACKFLOW |
| | FOR FOUNTAIN CONTRACTOR TO TIE INTO. |
| | 10) SHTS P2/P3 #40 DISHWASHER, TIE INTO |
| | SANITARY NOT GREASE PER UTILITY DEPT. |
| | 11) SHTS P2/P3 WITH DISHWASHER MOVED TO |
| | SANITARY A VENT IS REQUIRED IN GREASE |
| | LINE BEFORE THE LAST FLOOR DRAINS BY |
| | DISHWASHER AREA. |
| | 12) SHTS P2/P3 2" VENT FROM GREASE TRAP |
| | NOT REQUIRED AND DOES NOT MEET CODE FOR |
| | HORIZONTAL DRY VENTS PLEASE REMOVE. SPC |
| | SEC 708.1 |
| | 13) SHT P2 PLEASE SUPPLY MANUFACTURE |
| | INFO FOR WATER FILTER #6. FILTER SHALL |
| | BE NSF APPROVED. |
| | 14) SHT P2 PER MODEL COUNTYWIDE AMEND- |
| | MENTS TO SPC-94 SEC 607.7, ONLY 2 FIX- |
| | TURES ON 1/2" COLD WATER SUPPLY. (SEE |
| | ITEMS #'S 23/21 AND SINK P6 WITH GLASS |
| | FILLER. |
| | 15) SHTS P2/P3/P4 ALL INDIRECT WASTE |
| | SHALL BE DRAINED TO FLOOR SINK NOT TO |
| | FLOOR DRAINS. SEE F.D. BY WALK IN COOLER |
| | AND WATER HEATER DETAIL (P-12) F.D. |
| | SPC SEC 804.5 |
| | 16) SHTS P1/P2/P3 FLOOR DRAINS ARE REQ- |
| | UIRED IN STAFF TOILET ROOM #149B AND |
| | IN GANG BATH RM'S #109 & #115. SEC 409.4 |
| | 17) SHTS P2/P3 SINK P-6 AT GLASS FILLER |
| | STATION NOT VENTED PROPERLY. |
| | 18) SHT P3 SANITARY RISER DIAGRAM, VENT |
| | FOR 3-COMP. SINK DISPOSERS #35 & #41, & |
| | HAND SINK #26 NOT VENTED THROUGH THE |
| | ROOF AS REQUIRED. |
| | 19) SHTS P2/P3 2-WAY CLEAN OUT IS REQ- |
| | UIRED NEAR JUNCTION OF BLDG. DRAIN AND |
| | BLDG SEWER FOR GREASE LINE. SEC 710.2.2 |
| | 20) SHT P4, GREASE TRAP DETAIL NOT APP- |
| | ROVED. PLEASE SEE ATTACHED SHEET WITH |
| | APPROVED GREASE TRAP DETAIL FROM WPB |
| | UTILITY DEPT. |
| | 21) SEPARATE GREASE TRAP PERMIT REQUIRED |
| | PERMIT TO BE APPLIED FOR BY PROVIDER OF |
| | GREASE TRAP NOT PLUMBING CONTRACTOR. |
| | 22) SEPARATE GAS PERMIT REQUIRED. SEE |
| | ATTACHED GAS PERMIT REQUIREMENT SHEET. |
| | NOTE NUMBERS 1, 3, 6, 7, 8, 9, 10, 11, & |
| | 12 CIRCLED. INFORMATION REQUIRED FOR ALL |
| | CIRCLED NUMBERS FOR PLAN REVIEW. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER STANDARD |
| | GAS CODE. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER THE STANDARD GAS |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER STANDARD GAS CODE SEC. 305.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | CODE SECS. 402.4 THRU 402.4.4.7. NO 7"WC |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER THE STANDARD GAS CODE SECS |
| | 602 THRU 612. |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | STANDARD GAS CODE SEC. 402. |
| | 10. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | 11. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 23) SHTS A2.1/A2.4 PLEASE SHOW CLEAR |
| | FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |