2002-01-26 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN-
 ESS REGULATION HOTEL & RESTURANT DIV.
 FOR REVIEW AND COMMENTS BEFORE RESUBMIT-
 ING FOR PLAN REVIEW.
 2) SHT P2, PLEASE CONTACT RODNEY COMPO
 ENVIRONMENTAL COMPLIANCE (561) 837-4074
 FOR GREASE TRAP SIZE. WASTE ORD. #2938-
 96. SUBMIT REVIEW LETTER BEFORE RESUBMIT
 ING FOR PLAN REVIEW,
 3) PLEASE SUBMIT CALCULATIONS FOR MINIM-
 UM FACILITIES PER SPC TABLE 407 AND SEC
 407.1.3. SHOW DEDUCTED AREAS.
 4) PLEASE PROVIDE A WATER RISER DIAGRAM.
 SHOW PIPE SIZES, WATER HAMMER ARRESTORS
 LOCATION OF BACKFLOW PREVENTERS ECT.
 REDUCED PRESSURE BACKFLOW REQUIRED ON
 WATER SERVICE TO CLUBHOUSE.
 5) STORM RISER DIAGRAM REQUIRED. INCLUDE
 PIPE SIZES AND SQ FT ADDED FROM EACH
 DOWNSPOUT AND TRENCH DRAIN.
 6) SHT A2.1 & SHT P2, STAFF TOILET ROOM
 #149B, DOOR SHALL NOT SWING INTO CLEAR
 FLOOR SPACE OF LAV. FACBC SEC 4.22.2
 7) SHT A5.4 DETAIL #8 STAFF SINK TO
 COMPLY WITH FACBC SEC 4.24. SHOW DETAILS
 FOR ALL SUBSECTIONS.
 8) SHT A5.3 RM #129 DETAIL #1 HAIRCARE
 VACUUM BREAKER REQUIRED ON WATER SUPPLY
 6" ABOVE FLOOD RIM LEVEL.
 9) SHT A2.1 & P1 FOUNTAIN, PLUMBING
 CONTRACTOR TO SUPPLY VALVE AND BACKFLOW
 FOR FOUNTAIN CONTRACTOR TO TIE INTO.
 10) SHTS P2/P3 #40 DISHWASHER, TIE INTO
 SANITARY NOT GREASE PER UTILITY DEPT.
 11) SHTS P2/P3 WITH DISHWASHER MOVED TO
 SANITARY A VENT IS REQUIRED IN GREASE
 LINE BEFORE THE LAST FLOOR DRAINS BY
 DISHWASHER AREA.
 12) SHTS P2/P3 2" VENT FROM GREASE TRAP
 NOT REQUIRED AND DOES NOT MEET CODE FOR
 HORIZONTAL DRY VENTS PLEASE REMOVE. SPC
 SEC 708.1
 13) SHT P2 PLEASE SUPPLY MANUFACTURE
 INFO FOR WATER FILTER #6. FILTER SHALL
 BE NSF APPROVED.
 14) SHT P2 PER MODEL COUNTYWIDE AMEND-
 MENTS TO SPC-94 SEC 607.7, ONLY 2 FIX-
 TURES ON 1/2" COLD WATER SUPPLY. (SEE
 ITEMS #'S 23/21 AND SINK P6 WITH GLASS
 FILLER.
 15) SHTS P2/P3/P4 ALL INDIRECT WASTE
 SHALL BE DRAINED TO FLOOR SINK NOT TO
 FLOOR DRAINS. SEE F.D. BY WALK IN COOLER
 AND WATER HEATER DETAIL (P-12) F.D.
 SPC SEC 804.5
 16) SHTS P1/P2/P3 FLOOR DRAINS ARE REQ-
 UIRED IN STAFF TOILET ROOM #149B AND
 IN GANG BATH RM'S #109 & #115. SEC 409.4
 17) SHTS P2/P3 SINK P-6 AT GLASS FILLER
 STATION NOT VENTED PROPERLY.
 18) SHT P3 SANITARY RISER DIAGRAM, VENT
 FOR 3-COMP. SINK DISPOSERS #35 & #41, &
 HAND SINK #26 NOT VENTED THROUGH THE
 ROOF AS REQUIRED.
 19) SHTS P2/P3 2-WAY CLEAN OUT IS REQ-
 UIRED NEAR JUNCTION OF BLDG. DRAIN AND
 BLDG SEWER FOR GREASE LINE. SEC 710.2.2
 20) SHT P4, GREASE TRAP DETAIL NOT APP-
 ROVED. PLEASE SEE ATTACHED SHEET WITH
 APPROVED GREASE TRAP DETAIL FROM WPB
 UTILITY DEPT.
 21) SEPARATE GREASE TRAP PERMIT REQUIRED
 PERMIT TO BE APPLIED FOR BY PROVIDER OF
 GREASE TRAP NOT PLUMBING CONTRACTOR.
 22) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED GAS PERMIT REQUIREMENT SHEET.
 NOTE NUMBERS 1, 3, 6, 7, 8, 9, 10, 11, &
 12 CIRCLED. INFORMATION REQUIRED FOR ALL
 CIRCLED NUMBERS FOR PLAN REVIEW.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 3. TYPE OF GAS, (LP OR NATURAL)
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 CODE SECS. 402.4 THRU 402.4.4.7. NO 7"WC
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 23) SHTS A2.1/A2.4 PLEASE SHOW CLEAR
 FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377