Plan Review Notes
Plan Review Notes For Permit 01121692
Permit Number 01121692
Review Stop M
Sequence Number 1
Notes
Date Text
2002-01-28 00:00:00********************DENIED**************
  
  
 1.PLAN SHEET M1 INDICATES TYPE "B"
 FLUE VENT PLEASE PROVIDE DETAIL OF
 FLUE VENT PENETRATION THROUGH THE
 ROOF.
  
 2.PROVIDE CALCULATION FOR COMBUSTION
 AIR IN THE MECHANICAL ROOM.
  
 3.PROVIDE DETAIL FOR THE "SHAFT" FLUE
 DUCT.
  
 4.PLEASE PROVIDE MANUFACTURER
 SUBMTTIAL DATA FOR THE METALBESTOS
 FLUE DUCT.
  
 5.PLAN SHEET M2 ON THE HOOD DETAIL
 INDICATES 3" LIMITED COMBUSTIBLES &
 12" TO COMBUSTIBLES.AS PER 1997
 SMC 504.4, HOOD SHALL HAVE A MINIMUM
 CLEARANCE OF 18" FROM COMBUSTIBLE
 CONSTRUCTION & MAY BE REDUCED TO NOT
 LESS THAN 3" WHERE THE COMBUSTIBLE
 MATERIAL PROTECTED WITH MATERIALS AS
 APPROVED FOR 1 HR FIRE RESISTANCE.
  
 PLEASE NOTE ADDITIONAL PERMITS
 REQUIRED FOR HOOD, FIRE SUPRESSION &
 WALKIN COOLERS/FREEZERS.PROVIDE
 PLANS & MANUFACTURER SUBMTTAL DATA
 WITH PERMIT APPLICATION.
  
 6.PLEASE INDICATE SIZE, TERMINATION &
 MATERIAL OF FLUE DUCT FOR THE FIRE
 PLACE.
  
 7.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.