| 2002-01-28 00:00:00 | ********************DENIED************** |
| | |
| | |
| | 1.PLAN SHEET M1 INDICATES TYPE "B" |
| | FLUE VENT PLEASE PROVIDE DETAIL OF |
| | FLUE VENT PENETRATION THROUGH THE |
| | ROOF. |
| | |
| | 2.PROVIDE CALCULATION FOR COMBUSTION |
| | AIR IN THE MECHANICAL ROOM. |
| | |
| | 3.PROVIDE DETAIL FOR THE "SHAFT" FLUE |
| | DUCT. |
| | |
| | 4.PLEASE PROVIDE MANUFACTURER |
| | SUBMTTIAL DATA FOR THE METALBESTOS |
| | FLUE DUCT. |
| | |
| | 5.PLAN SHEET M2 ON THE HOOD DETAIL |
| | INDICATES 3" LIMITED COMBUSTIBLES & |
| | 12" TO COMBUSTIBLES.AS PER 1997 |
| | SMC 504.4, HOOD SHALL HAVE A MINIMUM |
| | CLEARANCE OF 18" FROM COMBUSTIBLE |
| | CONSTRUCTION & MAY BE REDUCED TO NOT |
| | LESS THAN 3" WHERE THE COMBUSTIBLE |
| | MATERIAL PROTECTED WITH MATERIALS AS |
| | APPROVED FOR 1 HR FIRE RESISTANCE. |
| | |
| | PLEASE NOTE ADDITIONAL PERMITS |
| | REQUIRED FOR HOOD, FIRE SUPRESSION & |
| | WALKIN COOLERS/FREEZERS.PROVIDE |
| | PLANS & MANUFACTURER SUBMTTAL DATA |
| | WITH PERMIT APPLICATION. |
| | |
| | 6.PLEASE INDICATE SIZE, TERMINATION & |
| | MATERIAL OF FLUE DUCT FOR THE FIRE |
| | PLACE. |
| | |
| | 7.PROVIDE AIR BALANCE SCHEDULE SHOWING |
| | COMPLIANCE WITH 1997 SMC 501.2. |
| | |