| Plan Review Notes For Permit 01121692 |
| Permit Number |
01121692 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-15 00:00:00 | 1) SITE PLAN DOES NOT INDICATE FIRE | | | HYDRANT LOCATIONS, FIRE MAINS, ETC. | | | 2) HOW IS FIRE RESCUE EXPECTED TO | | | ENTER THE GUARD HOUSE. WILL IT BE | | | STAFFED FULL TIME OR PART TIME. | | | 3) BUILDING ADDRESS REQUIRED ON | | | BUILDING. | | | 4) PANIC HARDWARE REQUIRED ON EXIT | | | DOORS. | | | 5) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 6) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER PLANS. | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FUTURE GENERATOR INSTALLATION. | | | 8) PROVIDE PRODUCT APPROVALS FOR FIRE | | | SHUTTER BETWEEN DINING 141 AND SERVICE | | | 142. | | | 9) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT AND EXTINGUISHING SYSTEM. | | | 10) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|