Plan Review Notes
Plan Review Notes For Permit 01121692
Permit Number 01121692
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-01-15 00:00:001) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATIONS, FIRE MAINS, ETC.
 2) HOW IS FIRE RESCUE EXPECTED TO
 ENTER THE GUARD HOUSE. WILL IT BE
 STAFFED FULL TIME OR PART TIME.
 3) BUILDING ADDRESS REQUIRED ON
 BUILDING.
 4) PANIC HARDWARE REQUIRED ON EXIT
 DOORS.
 5) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 6) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER PLANS.
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUTURE GENERATOR INSTALLATION.
 8) PROVIDE PRODUCT APPROVALS FOR FIRE
 SHUTTER BETWEEN DINING 141 AND SERVICE
 142.
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT AND EXTINGUISHING SYSTEM.
 10) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910