Plan Review Notes
Plan Review Notes For Permit 01121692
Permit Number 01121692
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-25 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING A "FUTURE" GENERATOR. PLEASE
 CLARFIY PLANS ARE SHOWING A EMER DIST
 SYSTEM AT THIS TIME. PLEASE CLARFIY
 IF EM LTS AND EXIT LTS ARE ARE BATTERY
 BACK UP, PLEASE SHOW ON FIXTURE SCHEDULE
 .700-12
  
 2)NOTE: PLEASE NOTE SPACING FOR GEN.
 DISC. REQ`D TO BE GROUPED WITH MAINS
 PER 230-72 ALSO PLEASE NOTE 230-76&79
 FOR DISCONNECT REQ`MENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW
 561-659-8096 EXT 8372