2002-01-29 00:00:00DENIED
 REFERENCE: SPC-94-FHA-AMEND 98
 DESIGN MANUAL
  
 1) SHT A4.01 NOTE STATES THAT 1ST FLOOR
 ONLY WILL BE ADAPTABLE. ALL UNITS OF ALL
 FLOORS SHALL BE ADAPTABLE PER FHA DESIGN
 MANUAL. (SEE PAGE #7 OF DESIGN MANUAL).
 2) DESIGN OPTION "A" OR "B" SHALL BE
 NOTED ON PLANS FOR ALL BATHROOMS.
 3) REQUIREMENTS 1 THRU 7 OF THE FHA-98
 DESIGN MANUAL SHALL BE REQUIRED FOR ALL
 UNITS.
 4) PLEASE SHOW CLEAR FROOR SPACE FOR ALL
 FIXTURES REQUIRED TO BE ADAPTABLE.
 5) SHT A8.03 DETAIL 14 BACKING IN BACK
 OF TUB/SHOWER NOT AS REQUIRED IN CHAPT.
 6 PAGE 6.9 OF FHA DESIGN MANUAL.
 6) SHTS P-1/P-3/P-5/P-7 CLEAN-OUTS SHALL
 BE MAXIMUM OF 80' PER SPC SEC 710.2.4(2)
 7) SHTS P-1/P-3/P-5/P-7 RELIEF VENT RE-
 QUIRED ON AT LEAST ONE CONDENSATE LINE
 PER BLDG.
 8) SHTS P-9 THRU P-17 WATER ISOMETRIC
 RISERS. AIR CHAMBERS SHALL NOT BE USED,
 SEE SHT P-25 NOTE #16. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR FIXTURES
 IN AN "EFFECTIVE RANGE" NOT ON TOP OF
 DROPS AS SHOWN. INSTALL PER PDI-WH 201
 AND MANUFACTURES INSTALLATION INSTRUCT-
 IONS.
 9) SHT P-3 BRIDGEPORT DELUX MODEL IS K2
 OR 12 RISER PICKING UP LAV IN POWDER RM?
 10) SHT P-19 RISER "E" HAS 2" ON FLAT
 AND 3" RISER. PLEASE CLAIRFY
 11) SHT P-3 RISER "D1" 3 WATER CLOSETS
 ON 3" BLDG DRAIN NOT ALLOWED SPC TABLE
 714.1 FOOTNOTE #3
 12) SHT P-18 RISER "R" AIR CHAMBER SHALL
 BE ACCESSIBLE AND RECHARGEABLE PER PDI-
 WH 201 AND SPC SEC 607.8.3. PLEASE SHOW
 DETAILS.
 13) SHT P-18 RISERS, CONDENSATE VENT
 SHALL NOT TERMINATE IN PLENUM FOR A/C
 PLEASE SHOW DETAIL FOR TERMINATION OF
 VENT FOR CONDENSATES.
  