| Plan Review Notes For Permit 01121691 |
| Permit Number |
01121691 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-24 00:00:00 | APARTMENTS TYPE I, II, III, IVA | | | | | | 1.PLAN SHEET A8.04 DETAIL #16, REF. | | | DETAIL #11 & 12 ON PLAN SHEET A8.05, | | | DETAIL #11 DRYWALL RETURN @ BATHTUB | | | & #12 DOES NOT EXIST.PLEASE | | | CLARIFY. | | | | | | 2.DRYER VENT WILL NOT COMPLY WITH 1997 | | | SBC 705.2.3.3,DRYER VENT CONTAINS | | | COMBUSTIBLE LINT. | | | | | | 3.DETAIL OF DUCT PENETRATING SHAFT | | | (A8.04), SHOWS DUCT PENETRATION AT | | | A 45 DEGREE ANGLE.UL LISTING DOES | | | NOT INDICATE THIS APPLICATION AS | | | BEING APPROVED. | | | | | | 4.PLEASE PROVIDE ELEVATION DETAIL OF | | | SHAFTS OF THE DRYER AND TOILET | | | EXHAUST, SPECIFY IF THE DUCTSARE | | | RUNNING INDIVIDUALLY IN THE SHAFT. | | | | | | DRYER VENTS SHALL BE NON-SCREENED | | | WITH A BACKDRAFT DAMPER. TOILET | | | EXHAUST SHALL BE SCREENED. |
|