| Plan Review Notes For Permit 01121691 |
| Permit Number |
01121691 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-28 00:00:00 | ******************** UNSAT ************* | | | | | | | | | 1)NOTE: PLEASE NOT ALL PANELS/SERVICE | | | EQUIPMENT ARE SHOWN ON PLANS. | | | PLEASE SHOW EXACT LOCATION OF MAIN SERV- | | | ICE ON FLOOR PLAN. SHOWS 1LC,1LB, NO | | | 2LA AND 1LA.? | | | 2)NOTE: PLEASE NOTE CIRCUITS #`S NEED TO | | | BE IDENTIFIED TO PANELS AND SHOWN ON | | | FLOOR PLANS. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS FOR HOUSE PANELS NEED TO BE SHOWN | | | AT 125% | | | | | | 4)NOTE: PLEASE CLARIFY "SHUNT TRIP" FOR | | | MAIN. PLEASE SEE 230-76 AND 230-79 FOR | | | MANUAL MEANS OF DISC REQ`D. | | | | | | 5)NOTE: PLEASE CLARIFY 30' GROUND ROD | | | SHOWN ON RISER DIAGRAM. | | | | | | 6)NOTE: PLEASE NOTE ALL HEIGHT REQ`MENTS | | | NEED TO BE SHOWN ON PLANS. PLEASE SEE | | | FHAR, 24 CFR 100.205 CHAPTER 5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|