Plan Review Notes
Plan Review Notes For Permit 01121619
Permit Number 01121619
Review Stop B
Sequence Number 2
Notes
Date Text
2002-07-10 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PRODUCT APPROVALS FROM TWO DIFFERENT
 STORM PANEL COMPANIES WERE SUBMITTED.
 PLEASE INDICATE WHICH ONE YOU WILL BE
 USING AND REMOVE THE OTHER. NOTE THE
 PRODUCT APPROVAL FOR THE EASTERN METAL
 SUPPLY STORM PANELS ARE NOT COMPLETE.
  
 3) INDICATE THE INSTALLATION OPTIONS
 THAT WILL BE USED BY CIRCLING THEM ON
 THE PRODUCT APPROVAL DRAWINGS.
  
 4) TAPCONS ARE NOT AN ACCEPTABLE ANCHOR
 FOR ATTACHMENT TO WOOD FRAME
 INSTALLATIONS. SEE SHEET 6 OF THE TOWN &
 COUNTRY PRODUCT APPROVAL.
  
 5) THE INSTALLATION SCHEDULE IS NOT
 FILLED OUT CORRECTLY. PLEASE REVISE.
 - THE SHUTTER HEIGHT WILL BE A MINIMUM
 OF 1-1/2" LARGER THAN THE OPENING DUE TO
 THE 3/4" EDGE DISTANCE REQUIREMENT FOR
 FASTENERS.SEE SHEET 6.
 - THE SHUTTER SPAN IS THE OPENING
 DIMENSION PARALLEL TO THE DIRECTION THE
 SHUTTER IS MOUNTED.
 - NO STORM BARS ARE REQUIRED FOR THE
 SPANS INDICATED.
 - NO HEADER REINFORCEMENT OR STORM PANEL
 BOLTING WILL BE REQUIRED.
 TYPICALLY EACH WINDOW OPENING IS GIVEN A
 NUMBER AND EACH NUMBER IS LISTED IN THE
 SCHEDULE ALONG WITH THE INFORMATION FOR
 THAT OPENING. DOUBLE WINDOWS ARE LISTED
 AS ONE OPENING. I HAVE ATTACHED A COPY
 OF A KEY PLAN AND SCHEDULE FOR YOU TO
 USE AS A GUIDE.
  
 6) THE PRODUCT APPROVALS FOR THE WINDOW
 MULLIONS ARE NOT COMPLETE AND THE
 DRAWINGS ARE ILLEGIBLE. TWO COPIES ARE
 REQUIRED.
  
 7) IF YOU DO NOT WANT THE ELECTRICAL
 PERMIT AT THIS TIME, PLEASE INDICATE ON
 REQUEST FOR PROPOSAL (WORK DESCRIPTION)
 THAT ITEM #3 WILL BE APPLIED FOR UNDER A
 SEPARATE PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202