Plan Review Notes
Plan Review Notes For Permit 01121511
Permit Number 01121511
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-01-02 00:00:001) BOLLARDS INSTALLED NEAR FIRE HYDRANTS
 SHALL NOT INTERFERE WITH THE
 REQUIRED OPERATION OF THEM.
 2) THE CHLORINE BUILDING IS TO COMPLY
 WITH NFPA 430. EXAMPLES INCLUDE AN
 EMERGENCY PLAN, APPROPRIATE SIGNAGE,
 NO SMOKING SIGNAGE, EMPLOYEE
 INSTRUCTIONS, MANUAL FIREFIGHTING
 EQUIPMENT, WATER SUPPLIES AT 750 GALLONS
 PER MINUTE OF WATER OR 500 GALLONS
 PER MINUTE OF WATER IF SPRINKLER SYSTEMS
 ARE PLANNED. PLEASE REVIEW NFPA 430
 AND MAKE THE NECESSARY COMMENTS ON THE
 PLANS.
 3) PLEASE SEE STAIR DETAILS ON S-19.
 MAXIMUM RISE ON STAIRS IS 7 INCHES, AND
 MINIMUM TREADS TO BE AT LEAST 11 INCHES.
 4) PLEASE PROVIDE MORE DETAILS ON 5
 MILLION GALLON EQUALIZER TANK. PLEASE
 CLEARLY INDCATE WHAT IS STORED IN THE
 TANK, AND ANY ASSOCIATED PRESSURES,
 HEALTH HAZARDS, ETC.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910