| Notes |
| Date |
Text |
| 2002-03-26 00:00:00 | | | | REVIEW FOR THE HVAC ONLY.SEPARATE | | | PERMIT FOR THE REFRIGERATION & TANK. | | | | | | REFRIGERATION REQUIREMENTS: | | | | | | PROVIDE LOCATION OF ALL EQUIPMENT AS | | | SHOWN ON R-1. | | | | | | PROVIDE DETAIL OF STANDS FOR THE | | | CONDENSER UNITS. | | | | | | SHOW COMPLIANCE WITH CHAPTER 11 OF | | | THE 1997 SMC | | | - INDICATE CLASSIFICATION | | | - COMPLY WITH CLASSIFICATION REQUIREMENT | | | AS PER TABLE 1104A & TYPE OF SYSTEM | | | PER 1103. | | | - SHOW ALL CALCULATIONS FOR VENTILATION | | | NORMAL & EMERGENCY. | | | - INDICATE LOCATIONS FOR LEAK DETECTORS | | | AND BREATHING APPARATUS. | | | | | | WILL THERE BE A GENERATOR FOR EMERGENCY | | | POWER? | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|