Plan Review Notes
Plan Review Notes For Permit 01121500
Permit Number 01121500
Review Stop M
Sequence Number 2
Notes
Date Text
2002-03-26 00:00:00 
 REVIEW FOR THE HVAC ONLY.SEPARATE
 PERMIT FOR THE REFRIGERATION & TANK.
  
 REFRIGERATION REQUIREMENTS:
  
 PROVIDE LOCATION OF ALL EQUIPMENT AS
 SHOWN ON R-1.
  
 PROVIDE DETAIL OF STANDS FOR THE
 CONDENSER UNITS.
  
 SHOW COMPLIANCE WITH CHAPTER 11 OF
 THE 1997 SMC
 - INDICATE CLASSIFICATION
 - COMPLY WITH CLASSIFICATION REQUIREMENT
 AS PER TABLE 1104A & TYPE OF SYSTEM
 PER 1103.
 - SHOW ALL CALCULATIONS FOR VENTILATION
 NORMAL & EMERGENCY.
 - INDICATE LOCATIONS FOR LEAK DETECTORS
 AND BREATHING APPARATUS.
  
 WILL THERE BE A GENERATOR FOR EMERGENCY
 POWER?
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.