| 2002-03-21 00:00:00 | A) PLEASE INDICATE HOW THE PRESCRIPTIVE |
| | CODE REQUIREMENTS OF NFPA 51B, THE |
| | STANDARD FOR FIRE PREVENTION, DURING |
| | WELDING, CUTTING, AND OTHER HOT WORK |
| | WILL BE ACCOMPLISHED WITHIN THE |
| | BUILDING. FURTHER DEFINE "LIGHT DUTY |
| | REPAIR WORK" AS NOTED IN PLAN REVIEW |
| | RESPONSE. IS ANY ACETYLENE GAS PLANNED |
| | TO BE USED OR STORED IN THE BUILDING. |
| | B) COMPLAINCE WITH CITY CODE 3206-99 |
| | "HAZARDOUS MATERIALS MAY BE APPLICABLE |
| | TO THE SITE. A COMPLETE LIST OF |
| | POTENTIAL HAZARDOUS MATERIALS FROM |
| | COSTCO HAS NOT YET BEEN RECEIVED. |
| | C) THE AMMONIA TANK MECHANICAL |
| | REFRIGERATION SYSTEM MUST COMPLY WITH |
| | NFPA 1, CHAPTER 23, MECHANICAL |
| | REFRIGERATION. |
| | D) A MINIMUM OF TWO FIRE HYDRANTS ARE |
| | TO BE PROVIDED ON THE 12" WATER MAIN |
| | OUTSIDE OF THE COSTCO WAREHOUSE FOR |
| | THE FUTURE EDITIONS OF THE BUILDING. |
| | E) PALLET STORAGE AREA- ARE THESE |
| | EMPTY, FULL, PLASTIC, OR WOOD PALLETS. |
| | F) COULD NOT LOCATE ANY FIRE ALARM |
| | HORN STROBES IN WAREHOUSE AREA. |
| | G) IS AN EMERGENCY GENERATOR PLANNED |
| | FOR THE SITE IN THE EVENT OF LOSS OF |
| | POWER. |
| | H) THE FIRE ALARM SYSTEM TO BE CLASS A |
| | OR FULLY ADDRESSABLE. |
| | I) IT IS RECOMMENDED THAT ANOTHER TAP |
| | BE MADE ON THE 12" LINE SO A REDUNCY |
| | IS PRESENT AND ALSO WITH THE FUTURE |
| | EDITIONS ANTICIPATED. |
| | K) PLEASE CLEARLY INDICATE ALL EMERGENCY |
| | LIGHT FIXURES IN MAIN WAREHOUSE AREA. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |