| Plan Review Notes For Permit 01121500 |
| Permit Number |
01121500 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-21 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW GROUNDING FOR GUARD | | | BOOTH AND PUMP BLDG ON LINE DIAGRAM.IT | | | IS NOTED GRND DETAIL IS SHOWN ON 4.2 | | | | | | 2)NOTE: PLEASE PROVIDE INFORMATION | | | ON FIRE PUMP. PLEASE CLARIFY PUMP SHOWN | | | COMING FROM PANEL P-10? PLEASE SEE | | | 695-3A. PLEASE CLARIFY SHOWN ONLY AS | | | 20A 1POLE? | | | | | | | | | | | | | | | 3)NOTE: PLEASE CLARIFY IF THERE IS | | | GOING TO BE ANY EMERGENCY GENERATOR ON | | | SITE? IF POWER GOES DOWN, HOW IS ALL | | | COLD STORAGE GOING TO GET POWER? | | | | | | 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | FOR ANYTHING THAT MAY DIRECTLY LINK ANY | | | CHANGES IN ELECTRICAL PLANS. IE, GENER. | | | FIRE PUMP, ETC. | | | | | | 5)NOTE: PLEASE NOTE, NOTE #4 FROM FIRST | | | REVIEW. PLEASE CLARIFY WHERE CONTINUOUS | | | LOADS ARE SHOWN AT 125% AND LARGEST | | | MOTOR LOAD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 6)NOTE: PLEASE NOTE WRONG COLOR CODING | | | FOR CONDUCTORS IN SPEC BOOKS. PLEASE | | | NOTE THAT PER LOCAL AMENDMENTS(215) | | | 277/480 IS BROWN/ PURPLE/ YELLOW.. |
|