| Date |
Text |
| 2002-01-24 00:00:00 | DENIED |
| | REFERENCE: SPC-94-FACBC-97 |
| | |
| | 1) SHT G1.01 SINGLE ACCOMMODATION TOILET |
| | FACILITIES. #'7 & 8, CENTER LINE OF W/C |
| | TO BE 18" OFF WALL NOT 15" TO 19" OFF |
| | GRAB BAR. FACBC FIG. 28. |
| | 2) SHT IR 7 OF 7. SEPARATE IRRIGATION |
| | PERMIT REQUIRED. BACKFLOW INSTALLED BY |
| | PLUMBING CONTRACTOR REQUIRED. |
| | 3) SHT A1.05. WATER HEATER REQUIRES A |
| | PERMINATE SHIPS LADDER TO MAKE IT READ- |
| | ILY ACCESSIBLE. SPC SEC 501.7 |
| | 4) SHTS A5.01/A5.02/M3.1/M3.2. STALL FOR |
| | HANDICAP SHALL HAVE A LAV INSIDE STALL. |
| | FACBC FIG 30(E). SHOW CLEAR FLOOR SPACE |
| | FOR ALL HDCP FIXTURES. |
| | 5) SHT M2.2 SEPARATE GAS PERMIT REQUIRED |
| | SEE ATTACHED SHEET FOR GAS PERMIT APPLI- |
| | CATION REQUIREMENTS. PLEASE PROVIDE ALL |
| | INFORMATION FOR PLAN REVIEW. |
| | 6) SHT M2.2 COLS. B/15-17-19-21, UNABLE |
| | TO IDENTIFY AG-1. PLEASE CLAIRFY DESIGN- |
| | ATION FOR. |
| | 7) SHT M3.1 SHIPPING EMPLOYEES REST ROOM |
| | PLUMBING PLAN, GAS OVERHEAD SHOWS 3/4", |
| | BUT DROP TO HEATER SHOWS 1" PLEASE |
| | CLAIRFY. |
| | 8) SHTS M3.1/M3.2/M3.3 ALL CONDENSATE |
| | SHALL BE PIPED TO DRYWELL OR STORM OUT- |
| | SIDE OF BLDG NOT INTO SANITARY AS SHOWN. |
| | A RELIEF VENT 6" ABOVE GRADE IS REQUIRED |
| | 9) SHT M3.1 SHIPPING EMPLOYEES REST ROOM |
| | WASTE AND VENT PLAN, ALL FLOOR DRAINS |
| | SHALL BE A MINIMUM OF 3" PER SPC SEC |
| | 409.4.1.1 (SEE SHTS M6.1 & M6.3 [D-1] & |
| | [D-3] ALSO). THIS IS TYPICAL FOR RECIEV- |
| | ING EMPLOYEES REST ROOM ALSO. |
| | 10) SHT M2.2 SAND INTERCEPTOR, AND SHT |
| | M3.3 TRENCH DRAIN FOR ENGINE ROOM AND |
| | BATTERY CHARGING AREA. PLEASE CONTACT |
| | RODNEY COMPO, (561) 837-4074, ENVIRON- |
| | MENTAL COMPLIANCE AT THE REGIONAL SEWER |
| | AND WASTE WATER TREATMENT PLAND FOR SIZ- |
| | ING OF THE SAND INTERCEPTOR AND TO SEE |
| | IF A DILLUTION TANK IS REQUIRED FOR |
| | POSSIBLE ACID SPILL FROM BATTERIES. |
| | 11) SHT M3.3 ENGINE ROOM, BACKFLOW TO BE |
| | MAXIMUM OF 4' OFF THE FLOOR FOR SERVICE. |
| | 12) SHT M3.3 ENGINE ROOM PLUMBING PLAN, |
| | PLEASE INDICATE WHAT IS BEING DRAINED IN |
| | THE -W- LINE FROM ROOM OVERHEAD. |
| | 13) DRINKING FOUNTAINS SHALL COMPLY WITH |
| | FACBC SEC 4.15 AND SEC 4.1.3(10) FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 14) PER SPC TABLE 407 PLEASE SUBMIT |
| | OCCUPANT CONTENT PER SHIFT, SUBSTANTIAT- |
| | ED BY OWNER, FOR DRY/COLD STORAGE COMBO. |
| | ALSO SEE SEC 407.3.2 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |