Plan Review Notes
Plan Review Notes For Permit 01121500
Permit Number 01121500
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT G1.01 SINGLE ACCOMMODATION TOILET
 FACILITIES. #'7 & 8, CENTER LINE OF W/C
 TO BE 18" OFF WALL NOT 15" TO 19" OFF
 GRAB BAR. FACBC FIG. 28.
 2) SHT IR 7 OF 7. SEPARATE IRRIGATION
 PERMIT REQUIRED. BACKFLOW INSTALLED BY
 PLUMBING CONTRACTOR REQUIRED.
 3) SHT A1.05. WATER HEATER REQUIRES A
 PERMINATE SHIPS LADDER TO MAKE IT READ-
 ILY ACCESSIBLE. SPC SEC 501.7
 4) SHTS A5.01/A5.02/M3.1/M3.2. STALL FOR
 HANDICAP SHALL HAVE A LAV INSIDE STALL.
 FACBC FIG 30(E). SHOW CLEAR FLOOR SPACE
 FOR ALL HDCP FIXTURES.
 5) SHT M2.2 SEPARATE GAS PERMIT REQUIRED
 SEE ATTACHED SHEET FOR GAS PERMIT APPLI-
 CATION REQUIREMENTS. PLEASE PROVIDE ALL
 INFORMATION FOR PLAN REVIEW.
 6) SHT M2.2 COLS. B/15-17-19-21, UNABLE
 TO IDENTIFY AG-1. PLEASE CLAIRFY DESIGN-
 ATION FOR.
 7) SHT M3.1 SHIPPING EMPLOYEES REST ROOM
 PLUMBING PLAN, GAS OVERHEAD SHOWS 3/4",
 BUT DROP TO HEATER SHOWS 1" PLEASE
 CLAIRFY.
 8) SHTS M3.1/M3.2/M3.3 ALL CONDENSATE
 SHALL BE PIPED TO DRYWELL OR STORM OUT-
 SIDE OF BLDG NOT INTO SANITARY AS SHOWN.
 A RELIEF VENT 6" ABOVE GRADE IS REQUIRED
 9) SHT M3.1 SHIPPING EMPLOYEES REST ROOM
 WASTE AND VENT PLAN, ALL FLOOR DRAINS
 SHALL BE A MINIMUM OF 3" PER SPC SEC
 409.4.1.1 (SEE SHTS M6.1 & M6.3 [D-1] &
 [D-3] ALSO). THIS IS TYPICAL FOR RECIEV-
 ING EMPLOYEES REST ROOM ALSO.
 10) SHT M2.2 SAND INTERCEPTOR, AND SHT
 M3.3 TRENCH DRAIN FOR ENGINE ROOM AND
 BATTERY CHARGING AREA. PLEASE CONTACT
 RODNEY COMPO, (561) 837-4074, ENVIRON-
 MENTAL COMPLIANCE AT THE REGIONAL SEWER
 AND WASTE WATER TREATMENT PLAND FOR SIZ-
 ING OF THE SAND INTERCEPTOR AND TO SEE
 IF A DILLUTION TANK IS REQUIRED FOR
 POSSIBLE ACID SPILL FROM BATTERIES.
 11) SHT M3.3 ENGINE ROOM, BACKFLOW TO BE
 MAXIMUM OF 4' OFF THE FLOOR FOR SERVICE.
 12) SHT M3.3 ENGINE ROOM PLUMBING PLAN,
 PLEASE INDICATE WHAT IS BEING DRAINED IN
 THE -W- LINE FROM ROOM OVERHEAD.
 13) DRINKING FOUNTAINS SHALL COMPLY WITH
 FACBC SEC 4.15 AND SEC 4.1.3(10) FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 14) PER SPC TABLE 407 PLEASE SUBMIT
 OCCUPANT CONTENT PER SHIFT, SUBSTANTIAT-
 ED BY OWNER, FOR DRY/COLD STORAGE COMBO.
 ALSO SEE SEC 407.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377