Date Text
2002-01-12 00:00:00 
 PHASE I
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89. (FOR ALL AREAS)
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PLAN SHEET M4.1 AC 2 IS SERVICING
 THE SHIPPING OFFICE.AC 1 IS
 SERVING THE RECEIVING OFFICE.THE
 SCHEDULE ON M-6.1 EQUIPMENT SCHEDULE
 DOES NOT COINCIDE WITH FLOOR PLAN.
  
 PLEASE INDICATE DUCT SMOKE DETECTORS
 ON PLAN SHOWING COMPLIANCE WITH 1997
 SMC 406.1
  
 5.CLARIFY RGF- SCHEDULE REFLECTS RGF
 AS BEING A RETURN GRILL WITH FIRE
 DAMPER.PLAN SHEET M-4.1 INDICATES
 2 TOTAL RGF ONE IN RECEIVING & 1 IN
 SHIPPING.ARE THEY FIRE DAMPERS OR
 BACKDRAFT DAMPERS?INDICATE ANY &
 ALL FIRE DAMPERS ON PLAN AS PER 1997
 SMC 610.6.
  
 6.PROVIDE INFORMATION ON THE ENGINE
 ROOM.INDICATE VENTILATION REQUIRE-
 MENTS FOR NORMAL OPERATION AS WELL
 AS EMERGENCY OPERATIONS.PROVIDE
 SEQUENCE OF OPERATION.
  
 ADDITIONAL PERMITS REQUIRED FOR ANY
 HOOD, FIRE SUPRESSION, FUEL AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLAN
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 PLEASE NOTE REFRIGERATION SHALL COMPLY
 WITH 1997 SMC CHAPTER 11 AND ASHRAE 15.
  
  