| 2001-12-26 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO,DURING AND AFTER CONSTRUCTION. |
| | 2) SUITABLE ROADS ARE TO BE PROVIDED |
| | AT THE SITE FOR EMERGENCY PURPOSES FOR |
| | FIRE AND PARAMEDICAL EQUIPMENT. |
| | 3) GUARD BOOTH CANOPY SHALL BE AT LEAST |
| | 13'- 6" HIGH IF FIRE APPARATUS ARE |
| | EXPECTED TO PASS UNDERNEATH IT. |
| | 4) FIRE HYDRANTS ARE TO BE INSTALLED TO |
| | UTILITY AND FIRE RESCUE STANDARDS. |
| | 5) ALL SECURITY GATES ARE TO BE PROPERLY |
| | PERMITTED. ANY ELECTRIC GATES MUST |
| | HAVE PROVISIONS FOR WHEN LOSS OF POWER |
| | OCCURS. |
| | 6) TAMPER SWITCHES, CHAINS AND LOCKS |
| | WILL BE REQUIRED ON ALL BACKFLOW |
| | DEVICES. |
| | 7) FIRE HYDRANT THREADS ARE TO BE |
| | COMPATIBLE WITH WEST PALM BEACH FIRE |
| | RESCUE STANDARDS. |
| | 8) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR UNDERGROUND TANK SHOWN ON PAGE A1.01 |
| | 9) MORE DETAILS NEEDED ON BATTERY |
| | CHARGING AREA. ARE ANY NOXIUOS FUMES |
| | OR PRODUCTS PRODUCED WHILE THE BATTERIES |
| | ARE BEING CHARGED. |
| | 10) PLEASE INDICATE HOW ITEMS WILL BE |
| | STORED. WHAT WILL THE MAXIMUM STORAGE |
| | HEIGHTS BE. |
| | 11) PLEASE EXPLAIN WELDING RECEPTACLES. |
| | 12) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR ALL |
| | AREAS OF THE BUILDING. |
| | 13) PLEASE EXPLAIN DRY SPRINKLER SYSTEMS |
| | WHY IS A WET FIRE SPRINKLER SYSTEM NOT |
| | SHOWN THROUGHOUT THE BUILDING. |
| | 14) NO HYDRAULIC CALCULATIONS PROVIDED |
| | WITH PLANS. |
| | 15) PLEASE EXPLAIN THE REASON FOR ALL |
| | OF THE END OF LINE RESISTORS SHOWN. |
| | 16) NOTES ON FP1 WITH REGARDS TO |
| | WATER STORAGE TANK NOT CLEAR. PLEASE |
| | EXPLAIN RATIONALE. WHAT BASIS IS THESE |
| | NOTES PROVIDED FOR. |
| | 17) WILL THE GUARD HOUSE BE STAFFED |
| | FULL TIME, PART TIME, ETC. |
| | 18) PLEASE PROVIDE A LIST OF ANY AND |
| | ALL HAZARDOUS MATERIALS PLANNED FOR |
| | THE BUILDING. |
| | 19) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEM. IT APPEARS |
| | THAT A MEETING WILL BE REQUIRED WITH |
| | REGARDS TO THE FIRE SPRINKLER DESIGN |
| | PLANNED FOR THE BUILDING. |
| | 20) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. CUT SHEETS, |
| | WIRING DIAGRAMS, BATTERY CALCULATIONS |
| | WILL BE REQUIRED. |
| | 21) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FUEL TANK. |
| | 22) A DESIGNATED FIRE LANE WILL BE |
| | REQUIRED FOR THE BUILDING. |
| | |