2001-12-26 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 2) SUITABLE ROADS ARE TO BE PROVIDED
 AT THE SITE FOR EMERGENCY PURPOSES FOR
 FIRE AND PARAMEDICAL EQUIPMENT.
 3) GUARD BOOTH CANOPY SHALL BE AT LEAST
 13'- 6" HIGH IF FIRE APPARATUS ARE
 EXPECTED TO PASS UNDERNEATH IT.
 4) FIRE HYDRANTS ARE TO BE INSTALLED TO
 UTILITY AND FIRE RESCUE STANDARDS.
 5) ALL SECURITY GATES ARE TO BE PROPERLY
 PERMITTED. ANY ELECTRIC GATES MUST
 HAVE PROVISIONS FOR WHEN LOSS OF POWER
 OCCURS.
 6) TAMPER SWITCHES, CHAINS AND LOCKS
 WILL BE REQUIRED ON ALL BACKFLOW
 DEVICES.
 7) FIRE HYDRANT THREADS ARE TO BE
 COMPATIBLE WITH WEST PALM BEACH FIRE
 RESCUE STANDARDS.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR UNDERGROUND TANK SHOWN ON PAGE A1.01
 9) MORE DETAILS NEEDED ON BATTERY
 CHARGING AREA. ARE ANY NOXIUOS FUMES
 OR PRODUCTS PRODUCED WHILE THE BATTERIES
 ARE BEING CHARGED.
 10) PLEASE INDICATE HOW ITEMS WILL BE
 STORED. WHAT WILL THE MAXIMUM STORAGE
 HEIGHTS BE.
 11) PLEASE EXPLAIN WELDING RECEPTACLES.
 12) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR ALL
 AREAS OF THE BUILDING.
 13) PLEASE EXPLAIN DRY SPRINKLER SYSTEMS
 WHY IS A WET FIRE SPRINKLER SYSTEM NOT
 SHOWN THROUGHOUT THE BUILDING.
 14) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH PLANS.
 15) PLEASE EXPLAIN THE REASON FOR ALL
 OF THE END OF LINE RESISTORS SHOWN.
 16) NOTES ON FP1 WITH REGARDS TO
 WATER STORAGE TANK NOT CLEAR. PLEASE
 EXPLAIN RATIONALE. WHAT BASIS IS THESE
 NOTES PROVIDED FOR.
 17) WILL THE GUARD HOUSE BE STAFFED
 FULL TIME, PART TIME, ETC.
 18) PLEASE PROVIDE A LIST OF ANY AND
 ALL HAZARDOUS MATERIALS PLANNED FOR
 THE BUILDING.
 19) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM. IT APPEARS
 THAT A MEETING WILL BE REQUIRED WITH
 REGARDS TO THE FIRE SPRINKLER DESIGN
 PLANNED FOR THE BUILDING.
 20) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. CUT SHEETS,
 WIRING DIAGRAMS, BATTERY CALCULATIONS
 WILL BE REQUIRED.
 21) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUEL TANK.
 22) A DESIGNATED FIRE LANE WILL BE
 REQUIRED FOR THE BUILDING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910