| 2002-01-09 00:00:00 | ******************UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE METHOD GROUNDING |
| | TRANSFORMER PER 250-30 PLANS SHOW COLD |
| | WATER PIPE. PLEASE NOTE THAT BREAKS IN |
| | THE LINE FOR WATER FROM REPAIRS ETC TO |
| | PVC AND CAUSE IMPROPER GOUNDING. PLEASE |
| | HAVE GROUNDING OF TRANSFOMER GO TO A |
| | NEAREST BLDG.STRUC STEEL. |
| | |
| | 2)NOTE: PLEASE CLARFIY, PLAN SHOWS |
| | FROM "MSB-1" COMPRESSORS BY HUSSMAN? |
| | PLEASE NOTE DETAIL NEEDS TO BE SHOWN |
| | ON THESE PLANS OR SEPARATE PLANS AND |
| | PERMIT APPLICATION NEED TO BE SUBMITTED |
| | FOR REVIEW. PLEASE CLARIFY IF THESE |
| | ARE FOR FUTURE OR WILL BE INSATLLED |
| | AT THE SAME TIME OF THIS BEING BUILT? |
| | |
| | 3)NOTE: PLEASE OCP FOR PANEL "P8", SHOWS |
| | A 200A/3P AND 110 AF. PLEASE CLARIFY |
| | "AF" AND NOTE CONDUCTOR SIZE RATED AT |
| | 130AMPS. |
| | |
| | 4)NOTE: PLEASE NOTE, LOAD CALCUALTIONS |
| | NEED TO BE SHOWN PER 220-2,220-10,220-11 |
| | 220-13. |
| | PLEASE NOTE THAT ALL CONTINUOUS LOADS |
| | NEED TO BE SHOWN AT 125%. PER 230-42, |
| | 215-3. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |