Plan Review Notes
Plan Review Notes For Permit 01121500
Permit Number 01121500
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-22 00:00:00THE FIRE PROTECTION PLANS ARE
 INCOMPLETE.PLEASE PROVIDE PLANS IN
 ACCORDANCE WITH CHAPTER 8 OF NFPA 13-99.
  
 GIVEN THAT THE COMMODITIES TO BE STORED
 ARE CLASS IV, SOME OF THE QUANTITIES MAY
 NEED TO BE STORED IN CONTROL AREAS AS
 PROVIDED FOR IN SBC 312.2.3 AND SBC 407.
 1.
  
 PLEASE SHOW DETAILS FOR
 THE BATTERY STORAGE RACKS AS TO
 VENTILATION AND SUPPORTING STRUCTURE.
 SEE SBC 411.1.2 (NEC 480)
  
 SHEETS A1.02, 1.03 AND 1.04.WHAT ARE
 THE PARALLEL LINES IN THE VICINITY OF
 GRID LINES A & B INDICATIVE OF?
  
 SHEET A1.02, KEY NOTE 15.WHERE IS THE
 PALLET STORAGE AREA? WHAT QUANTITY,
 VOLUME?
  
 PROVIDE INFORMATION FOR THE VINYL FACED
 INSULATION THAT WILL BE EXPOSED AS
 INTERIOR FINISH.SEE SBC 803.3
  
 THE ROOF SKYLIGHTS MUST COMPLY WITH SBC
 2604.6 AND THE CITY'S HURRICANE MISSILE
 IMPACT RESISTANCE REQUIREMENTS.
  
 SHEET S1.01 GENERAL NOTES IS NOT CLEAR
 AS TO WHICH DESIGN METHOD FOR WIND WAS
 USED, SBC 1606.2 OR ASCE 7-95. PLEASE
 DECLARE ONE.SEE SBC 1606.1.2.
  
 THE SPECIFICATIONS AND SOIL REPORTS
 WERE NOT INCLUDED WITH THE APPLICATION
 SO A COMPLETE CODE REVIEW IS NOT
 POSSIBLE.
  
 A RESIDENT INSPECTOR WILL BE REQUIRED
 FOR THIS PROJECT.CONTACT DON NEELY,
 ASSISTANT BUILDING OFFICIAL FOR MORE
 INFORMATION.561-659-8096 X 8333.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY FOR THE CITY, THE PERMIT
 PLANS STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 PLEASE PROVIDE A RECENT SIGNED, SEALED
 AND DATED PROPERTY SURVEY.