| Notes |
| Date |
Text |
| 2002-05-24 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | SHOWS MAIN DISC`S AND NOT SHOWN ON PLANS | | | PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE CLARIFY EQUIPMENT GROUND | | | BETWEEN MAIN AND PANEL.250-122 | | | | | | 3)NOTE: PLEASE NOTE AIC CALCS MENTION | | | RATINGS OF EACH PANEL AT 10,000. IS THIS | | | THE SAME FOR MAIN DISC`S SHOWN? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|