| Plan Review Notes For Permit 01121475 |
| Permit Number |
01121475 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | 1) BUILDING ADDRESSES REQUIRED. | | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | 3) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 4) ELECTRIC POWERED SMOKE DETECTORS | | | ARE REQUIRED. IT APPEARS THAT REQUIRED | | | SMOKE DETECTORS WITHIN THE BEDROOMS HAVE | | | BEEN OMITTED FROM THE PLANS. | | | 5) PLEASE IDENTIFY ALL EGRESS WINDOWS | | | ON THE PLANS AND MAXIMUM SILL HEIGHTS. | | | 6) PLEASE INDENTIFY INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | 7) THE C LABELED FIRE DOORS ARE | | | REQUIRED TO BE EQUIPPED WITH | | | SELF-CLOSING DEVICES. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|