2002-05-01 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SHT A-16 SANITARY RISER DIAGRAM FOR
 UNITS A & C, BATH #3 FROM UPPER UNIT
 SHALL NOT DRAIN PAST LAUNDRY SINK ON
 WASTE STACK. BATH #3 SHALL BE TAKEN OFF
 BELOW LAUNDRY SINK. (FROM PREVIOUS REV-
 IEW)
 2) SHT A-16 SANT RISER DIAG., M/BATH
 FROM UPPER UNIT SHALL NOT DRAIN INTO
 BRANCH LINE FOR FIRST FLOOR M/BATH. UP-
 PER M/BATH SHALL DRAIN INTO BLDG DOWN-
 STREAM OF M/BATH ON 1ST FLOOR.
 3) SHT A-16 SANT RISER DIAG., 4 FIXTURE
 UNITS MAXIMUM FOR 2" WET VENT IN MASTER
 BATH SANITARY. 3" PIPE REQUIRED TO STACK
 (ADDRESSED FOR 2ND FLOOR BUT NOT 1ST)
 4) SHT A-16 SANT RISER DIAG., SAME AS
 NOTE #1, BUT FOR RISER B & D.
 5) SHT A-16 SANT RISER DIAG., SAME AS
 NOTE #2, BUT FOR RISER B & D.
 6) SHT A-16 SANT RISER DIAG., SAME AS
 NOTE #3, BUT FOR RISER B & D>
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377