Plan Review Notes
Plan Review Notes For Permit 01121474
Permit Number 01121474
Review Stop R
Sequence Number 2
Notes
Date Text
2002-07-31 00:00:00DENIED
 SHOP DRAWINGS FOR SECOND FLOOR COVERED
 PORCH GUARD RAILS
  
 1) SECOND SHEET OF ENGINEERED DRAWINGS
 NOT SIGNED AND SEALED BY THE ENGINEER.
  
 2) THE PICKETS ON SHEET 2 ARE NOT THE
 SAME AS SHEET 1. HOW WILL PICKETS SHOWN
 ON SHEET 1 BE ATTACHED TO RAILS?
  
 3) SPECIFY THE TYPE OF 1/4"X 3" ANCHORS
 THAT WILL BE USED. TAPCONS?
  
 4) INDICATE HOW THE TOP RAIL OF THE
 GUARDRAIL WILL ATTACH TO WALL OF THE
 STRUCTURE AND TO THE 402 COLUMN. SPECIFY
 NUMBER AND TYPE OF FASTENERS.
  
 5) IN ADDITION TO WINDLOADS, GUARDRAILS
 MUST BE CAPABLE OF WITHSTANDING LOADS
 APPLIED TO THE TOP OF THE GUARDRAIL AND
 A CONCENTRATED HORIZONTAL LOAD AT ANY
 POINT IN THE GUARDRAIL SYSTEM INCLUDING
 INTERMEDIATE RAILS. SEE 2001 FBC SECT.
 1608.2.2.1 AND 1608.2.2.3 INDICATE THE
 LOADS THE GUARDRAIL IS CAPABLE OF
 WITHSTANDING ON THE DRAWINGS.