Plan Review Notes For Permit 01121474
Permit Number 01121474
Review Stop P
Sequence Number 2
Notes
Date Text
2002-03-14 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL.
  
 1) FROM PERVIOUS REVIEW - PLEASE SUBMIT
 MEASUREMENTS FOR WATER CLOSET OPENINGS
 IN MASTER BATH ALL UNITS. SHTS A-3/A-4
 2) SHT A-16 SANITARY RISER DIAGRAM FOR
 UNITS A & C. BATH #3 FROM UPPER UNIT CAN
 NOT DRAIN PAST LAUNDRY SINK ON WASTE
 STACK. BATH #3 SHALL BE TAKEN OFF BELOW
 LAUNDRY SINK.
 3) SHT A-16 SANT RISER DIAG, M/BATH FROM
 UPPER UNIT DRAINS INTO 2" SHOWER DRAIN.
 4) SHT A-16 SANT RISER DIAG, 4 FIXTURE
 UNITS MAXIMUM FOR 2" WET VENT IN MASTER
 BATH SANITARY. 3" PIPE REQUIRED TO STACK
 SEE NOTE #7 FROM PREVIOUS REVIEW.
 5) SHT A-16 SANT RISER DIAG. FOR UNITS
 B & D, NO LAUNDRY SINK SHOWN FOR UPPER
 UNIT.
 6) SHT A-16 SANT RISER DIAG, BATH #2
 DOES NOT REFLECT FLOOR PLAN. FLOOR PLAN
 SHOWS BATH #2 TAKEN OFF BLDG DRAIN BE-
 TWEEN WASHER-LAUNDRY SINK & KITCHEN, BUT
 RISER DIAGRAM SHOWS BATH #2 TAKEN OFF
 BEFORE WASHER-LAUNDRY SINK. PLSE CLAIRFY
 7) SHT A-16 SANT RISER DIAG, SAME AS
 NOTE #2 EXCEPT FOR RISER B & D.
 8) SHT A-16 SANT RISER DIAG, SAME AS
 NOTE #3 EXCEPT FOR RISER B & D.
  
 REVIEW BY KEN STEVENS