| Date |
Text |
| 2002-03-14 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FHA AMEND-98 DESIGN |
| | MANUAL. |
| | |
| | 1) FROM PERVIOUS REVIEW - PLEASE SUBMIT |
| | MEASUREMENTS FOR WATER CLOSET OPENINGS |
| | IN MASTER BATH ALL UNITS. SHTS A-3/A-4 |
| | 2) SHT A-16 SANITARY RISER DIAGRAM FOR |
| | UNITS A & C. BATH #3 FROM UPPER UNIT CAN |
| | NOT DRAIN PAST LAUNDRY SINK ON WASTE |
| | STACK. BATH #3 SHALL BE TAKEN OFF BELOW |
| | LAUNDRY SINK. |
| | 3) SHT A-16 SANT RISER DIAG, M/BATH FROM |
| | UPPER UNIT DRAINS INTO 2" SHOWER DRAIN. |
| | 4) SHT A-16 SANT RISER DIAG, 4 FIXTURE |
| | UNITS MAXIMUM FOR 2" WET VENT IN MASTER |
| | BATH SANITARY. 3" PIPE REQUIRED TO STACK |
| | SEE NOTE #7 FROM PREVIOUS REVIEW. |
| | 5) SHT A-16 SANT RISER DIAG. FOR UNITS |
| | B & D, NO LAUNDRY SINK SHOWN FOR UPPER |
| | UNIT. |
| | 6) SHT A-16 SANT RISER DIAG, BATH #2 |
| | DOES NOT REFLECT FLOOR PLAN. FLOOR PLAN |
| | SHOWS BATH #2 TAKEN OFF BLDG DRAIN BE- |
| | TWEEN WASHER-LAUNDRY SINK & KITCHEN, BUT |
| | RISER DIAGRAM SHOWS BATH #2 TAKEN OFF |
| | BEFORE WASHER-LAUNDRY SINK. PLSE CLAIRFY |
| | 7) SHT A-16 SANT RISER DIAG, SAME AS |
| | NOTE #2 EXCEPT FOR RISER B & D. |
| | 8) SHT A-16 SANT RISER DIAG, SAME AS |
| | NOTE #3 EXCEPT FOR RISER B & D. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |