2002-02-04 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-AMENDED-98
 DESIGN MANUAL
  
 1) ALL UNIT TYPES SHALL COMPLY WITH
 FAIR HOUSING ACT AMENDED 1998 DESIGN
 MANUAL REQUIREMENTS 1 THRU 7. INDICATE
 ON PLANS EITHER OPTION "A" OR "B" FOR
 BATHROOMS.
 2) SHOW CLEAR FLOOR SPACE FOR ALL FIX-
 TURES IN ALL UNITS PER FHA DESIGN MANUAL
 3) ALL WATER CLOSETS SHALL HAVE A MINI-
 MUM OPENING OF 2'9". SOME SHOW 2'8" AND
 SOME HAVE NO MEASURMENTS ON THEM. PLEASE
 SHOW DETAILS ON PLANS FOR PROPER W/C
 SPACE.
 4) PLEASE SEE FHA DESIGN MANUAL FOR LAV
 TO BE CENTERED ON PARALLEL APPROACH OR
 IF FRONTAL APPROACH SHOW REMOVABLE BASE
 CABINET. PLEASE PROVIDE DETAILS ON PLAN.
 5) SHT A-16 "A" PLUMBING RISER DIAGRAM,
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. LAUNDRY SINK NOT SHOWN, 1 BATHROOM
 MISSING, KITCHEN TO BE ON SAME SIDE OF
 UNIT AS W/M, WHY ISLAND VENT IN KITCHEN
 AND WHAT IS OTHER VENT BEFORE ISLAND
 VENT FOR?, 3" TO STACK IN MASTER BATH
 (ONLY 4 F.U. ON 2" WET VENT).
 6) SHT A-16 "B" PLUMBING RISER DIAGRAM.
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. LAUNDRY SINK NOT SHOWN, KITCHEN TO
 BE ON SAME SIDE OF UNIT AS W/M STK, WHY
 ISLAND VENT FOR KIT. AND WHAT IS VENT
 BEFORE ISLAND VENT FOR?, BATH #2 TO BE
 ON OTHER SIDE OF RISER DIAGRAM, 3" TO
 STACK IN M/BATH (ONLY 4 F.U. ON 2" WET
 VENT)
 7) SHT A-16 "C" PLUMBING RISER DIAGRAM.
 RISER DIAGRAM DOWS NOT REFLECT FLOOR
 PLAN. LAUNDRY SINK NOT SHOWN, KITCHEN
 SHALL BE ON SAME SIDE AS W/M, WHY ISLAND
 VENT FOR KIT. SINK AND WHAT IS VENT BE-
 FORE ISLAND SINK FOR?, 3" REQUIRED TO
 STACK FOR M/BATH (ONLY 4 F.U. ON 2" WET
 VENT.
 8) SHT A-16 "D" PLUMBING RISER DIAGRAM.
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. LANUDRY SINK NOT SHOWN, W/M AND
 BATH #2 TO BE ON LEFT SIDE OF RISER DIA.
 WITH M/BATH, KITCHEN SHALL BE ON RIGHT
 SIDE OF DIAG., WHY ISLAND VENT FOR KIT.
 SINK AND WHAT IS VENT BEFORE ISLAND VENT
 FOR?.
 9) IF UNITS ARE NOT INDIVIDUALLY METERED
 A RPZ BACKFLOW SHALL BE REQUIRED.
 10) PLEASE SUBMIT A FLAT DRAWING OF THE
 BLDG DRAIN AND COMPLETE RISER FOR SAME
 WITH PIPE SIZING. THIS WILL NOT BE REQ-
 UIRED IF EACH UNIT IS PIPED OUT OF BLDG
 INDIVIDUALLY.
  
 REVIEW BY KEN STEVENS