| 2002-02-05 00:00:00 | |
| | NO MECHANICAL PLANS SUBMITTED FOR |
| | REVIEW.PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION WITH MECHANICAL PLANS AND |
| | PERMIT. |
| | |
| | 1.DUCT LAYOUT - SIZE, MATERIAL, R - |
| | VALUE, AND CFM DISTRIBUTION. |
| | |
| | 2.PROVIDE GRILLE SIZE. |
| | |
| | 3.HVAC EQUIPMENT SCHEDULE - MAKE, |
| | MODEL, BTU, KW HEAT STRIP AND SEER |
| | OF THE CONDENSER. |
| | |
| | 4.INDICATE SIZE OF THE REFRIGERATION |
| | AND CONDENSATE LINES.PROVIDE |
| | PIPING LAYOUT FROM AHU TO CONDENSER. |
| | |
| | 5.CONDENSATE FROM UNITS LARGER THAN |
| | 3 TON SHALL TERMINATE INTO AN |
| | APPROVED DRYWELL OR STORM DRAIN. |
| | |
| | 6.PROVIDE DETAIL OF DRYER EXHAUST. |
| | INDICATE TERMINATION (ROOF OR WALL), |
| | ARE DUCTS IN A FIRE RATED CHASE? |
| | PLEASE NOTE AS PER 1997 SMC 509.3, |
| | MINIMUM SIZE 4" WITH A MAXIMUM |
| | LENGTH OF 25' (5' REDUCTION FOR EACH |
| | 90 DEGREE BEND & 2 1/2 REDUCTION FOR |
| | EACH 45 DEGREE BEND).WALL OR ROOF |
| | CAP SHALL BE NON SCREENED WITH A |
| | BACKDRAFT DAMPER. |
| | |
| | 7.BATHROOM EXHAUST - INDICATE DUCT |
| | SIZE, MATERIAL, AND TERMINATION. |
| | |
| | ALL ENVIRONMENTAL CONTROLS SHALL COMPLY |
| | WITH THE FAIR HOUSING ACT REGULATIONS, |
| | CHAPTER 5 FOR ACCESSIBLE LOCATION AND |
| | HEIGHT REQUIRMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |